- Part number
- METSECT5MC080
Description
About the METSECT5MC080
About the METSECT5MC080
The Schneider Electric METSECT5MC080 is a PowerLogic MC-type current transformer for panel metering, rated 800/5 A for busbar and cable installation. It accepts cables up to 32 mm in diameter or a 40.5 x 10.5 / 32.5 x 20.5 / 25.5 x 25.5 mm bus bar, delivering Class 0.5 accuracy at 10 VA burden or Class 1 at 12 VA.
Certifications & Standards
- CE
- VDE 0414
- IEC 61869-2
Selection Notes
The METSECT5MC080 carries 800 A primary current through the same 32 mm MC window used by the lower-current variants, with a 48 kA thermal rating that is the highest in the MC line. Choosing it over the 600 A unit makes sense once the feeder's fault current calculation shows the lower-rated core would saturate; the window size and mounting options stay identical across the family, so this is purely a current and thermal-duty decision.
Specification
Full specification
Main 6
| Range | PowerLogic |
|---|---|
| Product or component type | Current transformer |
| Product name | CT |
| Secondary current | 5 A |
| Accuracy class | Class 0.5 at 10 VA, Class 1 at 12 VA |
| [In] rated current | 800 A |
Complementary 19
| Current transformer type | Tropicalised for busbar and cable, Solid core |
|---|---|
| Current transformer ratio | 800/5 |
| [Ith] conventional free air thermal current | 48 kA |
| Dynamic withstand current | 2.5 Ith |
| Maximum safety factor | 5 |
| [Ue] rated operational voltage | < 720 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 3 kV 50 Hz for 1 minute |
| Mounting mode | By screws, Insulated locking screw, Clip-on |
| Mounting support | Busbar, Mounting plate, DIN rail |
| Width | Outside: 70 mm, Inner: 41 mm |
| Height | Outside: 95 mm, Inner: 41 mm |
| Depth | Frame : 45 mm, Total : 65 mm |
| Diameter | 32 mm |
| Net weight | 0.499 kg |
| [Uimp] rated impulse withstand voltage | 3 kV |
| Electrical insulation class | Class B |
| Cable outer diameter | 32 mm |
| Opening of bars | 40.5 x 10.5, 32.5 x 20.5, 25.5 x 25.5 |
| Sealing | Without |
Environment 5
| Standards | VDE 0414, IEC 61869-2 |
|---|---|
| Product certifications | CE |
| IP degree of protection | IP20 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -25…60 °C |
Show all 53 specifications ↓ Show less ↑23 more values in Identification, Contractual warranty, Logistics.
Identification 6
| Part number | METSECT5MC080 |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 16
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.200 cm |
| Package 1 Width | 7.200 cm |
| Package 1 Length | 11.200 cm |
| Package 1 Weight | 420.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 33 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 14.700 kg |
| Shipping weight | 0.499 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for METSECT5MC080
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- CE
- VDE 0414
- IEC 61869-2
Quick answers
Questions about the METSECT5MC080
What is the rated current of METSECT5MC080?
The rated current of METSECT5MC080 is 800 A.
What is the HS code of METSECT5MC080 for customs?
The tariff (HS) code on file for METSECT5MC080 is 850431.
Where does METSECT5MC080 ship from, and how fast?
METSECT5MC080 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.