- Part number
- METSECT5MB040
Description
About the METSECT5MB040
About the METSECT5MB040
The Schneider Electric METSECT5MB040 is a PowerLogic MB-type current transformer for panel metering, rated 400/5 A for busbar and cable installation. It accepts cables up to 26 mm in diameter or a 40.5 x 12.5 mm / 32.5 x 15.5 mm bus bar, and delivers Class 0.5 accuracy at 6 VA burden or Class 1 at 8 VA.
Certifications & Standards
- CE
- IEC 61869-2
- VDE 0414
Selection Notes
Choose the METSECT5MB040 when the feeder carries up to 400 A and the installation needs one CT that fits either a cable up to 26 mm or a bus bar, since its dual bar openings and cable window cover both without changing hardware. The 24 kA thermal rating and 2.5x Ith dynamic withstand keep the core from saturating during a downstream fault. Against the narrower-window MC-type units in the same tropicalised range, the MB040 is the pick when the conductor diameter exceeds 32 mm.
Specification
Full specification
Main 6
| Range | PowerLogic |
|---|---|
| Product or component type | Current transformer |
| Product name | CT |
| Secondary current | 5 A |
| Accuracy class | Class 0.5 at 6 VA, Class 1 at 8 VA |
| [In] rated current | 400 A |
Complementary 19
| Current transformer type | Tropicalised for busbar and cable, Solid core |
|---|---|
| Current transformer ratio | 400/5 |
| [Ith] conventional free air thermal current | 24 kA |
| Dynamic withstand current | 2.5 Ith |
| Maximum safety factor | 5 |
| [Ue] rated operational voltage | < 720 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 3 kV 50 Hz for 1 minute |
| Mounting mode | Insulated locking screw, By screws, Clip-on |
| Mounting support | Mounting plate, Busbar, DIN rail |
| Width | Outside: 60 mm |
| Height | Outside: 85 mm |
| Depth | Frame : 43 mm, Total : 63 mm |
| Diameter | 26 mm |
| Net weight | 0.348 kg |
| [Uimp] rated impulse withstand voltage | 3 kV |
| Electrical insulation class | Class B |
| Cable outer diameter | 26 mm |
| Opening of bars | 40.5 x 12.5, 32.5 x 15.5 |
| Sealing | Without |
Environment 5
| Standards | IEC 61869-2, VDE 0414 |
|---|---|
| Product certifications | CE |
| IP degree of protection | IP20 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -25…60 °C |
Show all 53 specifications ↓ Show less ↑23 more values in Identification, Contractual warranty, Logistics.
Identification 6
| Part number | METSECT5MB040 |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 16
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.200 cm |
| Package 1 Width | 7.000 cm |
| Package 1 Length | 9.200 cm |
| Package 1 Weight | 336.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 55 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 18.880 kg |
| Shipping weight | 0.348 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for METSECT5MB040
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- CE
- IEC 61869-2
- VDE 0414
Quick answers
Questions about the METSECT5MB040
What is the rated current of METSECT5MB040?
The rated current of METSECT5MB040 is 400 A.
What is the HS code of METSECT5MB040 for customs?
The tariff (HS) code on file for METSECT5MB040 is 850431.
Where does METSECT5MB040 ship from, and how fast?
METSECT5MB040 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.