- Part number
- METSECT5CC005
Description
About the METSECT5CC005
About the METSECT5CC005
The Schneider Electric METSECT5CC005 is a PowerLogic solid-core current transformer tropicalised for cable mounting, with a 50/5 A current ratio and a 21 mm cable window. It is rated Class 1 accuracy (Class 1 at 1.25 VA, Class 3 at 1.5 VA) with a 3 kA thermal withstand current, suitable for metering and protection-relay current inputs on DIN rail or mounting-plate panels.
Certifications & Standards
- CE
- VDE 0414
- IEC 61869-2
Selection Notes
Accuracy class sets the use case: this unit is supplied without a Class 0.5 tap, so it is suited to panel indication (Class 1) and protection-relay feeds (Class 3) rather than billing-grade metering. The 3 kA thermal withstand current scales with the 50 A rating, so moving to a higher-current sibling in the CC series also raises the short-circuit withstand available at the metering point — pick the ratio that matches the actual line current rather than the breaker frame size, since oversizing a CT ratio reduces measurement resolution at normal load.
Specification
Full specification
Main 6
| Range | PowerLogic |
|---|---|
| Product or component type | Current transformer |
| Product name | CT |
| Secondary current | 5 A |
| Accuracy class | Class 1 at 1.25 VA, Class 3 at 1.5 VA |
| [In] rated current | 50 A |
Complementary 18
| Current transformer type | Tropicalised for cable, Solid core |
|---|---|
| Current transformer ratio | 50/5 |
| [Ith] conventional free air thermal current | 3 kA |
| Dynamic withstand current | 2.5 Ith |
| Maximum safety factor | 5 |
| [Ue] rated operational voltage | < 720 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 3 kV 50 Hz for 1 minute |
| Mounting mode | Clip-on, By screws |
| Mounting support | Mounting plate, DIN rail |
| Width | Outside: 44 mm |
| Height | Outside: 65 mm |
| Depth | Frame : 30 mm, Total : 37 mm |
| Diameter | 21 mm |
| Net weight | 0.19 kg |
| [Uimp] rated impulse withstand voltage | 3 kV |
| Electrical insulation class | Class B |
| Cable outer diameter | 21 mm |
| Sealing | With |
Environment 5
| Standards | VDE 0414, IEC 61869-2 |
|---|---|
| Product certifications | CE |
| IP degree of protection | IP20 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -25…60 °C |
Show all 52 specifications ↓ Show less ↑23 more values in Identification, Contractual warranty, Logistics.
Identification 6
| Part number | METSECT5CC005 |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 16
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 5.500 cm |
| Package 1 Length | 8.400 cm |
| Package 1 Weight | 189.600 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 50 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.780 kg |
| Shipping weight | 0.19 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for METSECT5CC005
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- CE
- VDE 0414
- IEC 61869-2
Quick answers
Questions about the METSECT5CC005
What is the rated current of METSECT5CC005?
The rated current of METSECT5CC005 is 50 A.
What is the HS code of METSECT5CC005 for customs?
The tariff (HS) code on file for METSECT5CC005 is 850431.
Where does METSECT5CC005 ship from, and how fast?
METSECT5CC005 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.