Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Schneider Electric LV563550, EasyPact CVS630F, 3P 500 A, 36 kA at 380/415 V AC, MA trip
The Schneider Electric LV563550 is a 500 A EasyPact CVS630F moulded case circuit breaker for low-voltage distribution. Its MA trip unit gives magnetic-only short-circuit protection with an adjustable instantaneous threshold, and the 3-pole, 3D frame breaks 36 kA at 380/415 V AC under IEC 60947-2.
LV563550 uses a fixed-thermal, magnetic-only MA trip unit rather than an adjustable electronic unit, so overload protection for the 500 A rating is set at the factory and only the instantaneous threshold (6...13 x In) is field-adjustable -- a simpler, lower-cost choice where the motor or feeder's steady-state current is already known. Choose the F-frame breaking class (36 kA at 380/415 V) over a lower class whenever downstream prospective fault current exceeds a 36 kA threshold.
| Range | EasyPact |
|---|---|
| Range of product | EasyPact CVS400...630 |
| Product name | EasyPact CVS |
| Device short name | CVS630F |
| Product or component type | Circuit breaker |
| Device application | Motor |
| Poles description | 3P |
| Protected poles description | 3D |
| Earth leakage protection (Vigi add on) | Without |
| [In] rated current | 500 A at 40 °C |
| Network type | AC |
| Utilisation category | Category A |
| [Icu] Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit name | MA |
| Trip unit technology | Magnetic |
| Trip unit rating | 500 A at 40 °C |
| Protection type | Short-circuit protection (magnetic) |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
|---|---|
| Network frequency | 50/60 Hz |
| Breaking capacity code | F |
| [Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 15000 cycles |
| Electrical durability | 4000 cycles 415 V In conforming to IEC 60947-2 |
| Control type | Toggle |
| Instantaneous pick-up adjustment type Ii | Adjustable |
| Instantaneous pick-up adjustment range | 6...13 x In |
| Contact position indicator | Yes |
| Mounting support | Backplate |
| Mounting mode | Fixed |
| Upside connection | Front |
| Downside connection | Front |
| Connections - terminals | Screw connection |
| Connection pitch | 45 mm |
| Compatibility code | CVS630 |
| Width | 140 mm |
| Depth | 110 mm |
| Height | 255 mm |
| Net weight | 5.2 kg |
| Standards | EN 60947-2, IEC 60947-2 |
|---|---|
| Product certifications | GOST, IEC |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Part number | LV563550 |
|---|---|
| Type designation | CVS630F |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.0 cm |
| Package 1 Width | 24.4 cm |
| Package 1 Length | 30.0 cm |
| Package 1 Weight | 6.039 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 12.078 kg |
| Shipping weight | 5.2 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of CVS630F is 500 A.
The tariff (HS) code on file for CVS630F is 85362090.
CVS630F ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...