Schneider Electric CVS630F TM-D thermal-magnetic MCCB, 600 A, 36 kA Icu, distribution protection.
The Schneider Electric LV563306 is a 3-pole EasyPact CVS630F moulded case circuit breaker rated 600 A with a 36 kA breaking capacity (Icu) at 380/415 V AC. It uses a TM-D thermal-magnetic trip unit combining adjustable thermal overload with magnetic short-circuit protection for general distribution feeders. The breaker is fixed-mounted and carries IP40 front-face ingress protection.
The TM-D trip unit pairs an adjustable thermal overload element (Ir 0.7...1x In, thermal protection adjustment range 420...600 A) with a magnetic trip (4...8x In) in one device, so this CVS630F covers both overload and short-circuit duty without a separate relay - the configuration to pick over the MA (magnetic-only) version of the same frame when no downstream overload device is installed. Its 36 kA Icu at 380/415 V AC sets the fault-current ceiling for this breaking-code-F frame; move to a higher breaking-code letter if prospective fault current exceeds that rating.
| Range | EasyPact |
|---|---|
| Range of product | EasyPact CVS400...630 |
| Product name | EasyPact CVS |
| Device short name | CVS630F |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| Earth leakage protection (Vigi add on) | Without |
| [In] rated current | 600 A at 40 °C |
| Network type | AC |
| Utilisation category | Category A |
| [Icu] Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 600 A at 40 °C |
| Protection type | Short-circuit protection (magnetic), Overload protection (thermal) |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
|---|---|
| Network frequency | 50/60 Hz |
| Breaking capacity code | F |
| [Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 15000 cycles |
| Electrical durability | 4000 cycles 415 V In conforming to IEC 60947-2 |
| Control type | Toggle |
| Thermal protection adjustment range | 420…600 A |
| Long time pick-up adjustment type Ir | Adjustable |
| Long time pick-up adjustment range | 0.7...1 x In |
| Long time delay adjustment type | Fixed |
| Instantaneous pick-up adjustment type Ii | Adjustable |
| Instantaneous pick-up adjustment range | 4...8 x In |
| Contact position indicator | Yes |
| Mounting support | Backplate |
| Mounting mode | Fixed |
| Upside connection | Front |
| Downside connection | Front |
| Connections - terminals | Screw connection |
| Connection pitch | 45 mm |
| Compatibility code | CVS630 |
| Width | 140 mm |
| Depth | 110 mm |
| Height | 255 mm |
| Net weight | 5.2 kg |
| Standards | EN 60947-2, IEC 60947-2 |
|---|---|
| Product certifications | IEC, GOST |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Part number | LV563306 |
|---|---|
| Type designation | CVS630F |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.000 cm |
| Package 1 Width | 15.500 cm |
| Package 1 Length | 29.000 cm |
| Package 1 Weight | 5.318 kg |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 16.518 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 12 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 78.416 kg |
| Shipping weight | 5.2 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of CVS630F is 600 A.
The rated operational voltage of CVS630F is 440 V AC.
The tariff (HS) code on file for CVS630F is 85362090.
CVS630F ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...