ABB Emax 2 vs Schneider MTZ2 vs Siemens 3WL2: 1600-2500A ACB Comparison
Compare 1600-2500A ACB platforms: ABB Emax 2, Schneider MTZ2, Siemens 3WL2 on breaking capacity, trip units, endurance and lifecycle cost. Shop at Stoklink.
The Schneider Electric LV481015 is a VigiPacT TB35P closed toroid, a type B earth-leakage current sensor dedicated to VigiPacT RHB residual current protection and monitoring relays. It measures current up to 80 A with a 35 mm inner diameter and a 1/600 transformer ratio, weighing 0.390 kg.
The TB35P shares the TB35's 35 mm bore but is rated to 80 A instead of 63 A, giving more current headroom on the same conductor size; choose it over the standard TB35 when the protected circuit runs above 63 A. It mounts on either a plain backplate or a DIN rail and must pair with a compatible VigiPacT RHB relay.
| Range | VigiPacT |
|---|---|
| Device short name | TB35P |
| Product or component type | Earth leakage current sensor |
| Device application | Equipment monitoring and control |
| Range compatibility | VigiPacT RHB residual current protection relay, VigiPacT RHB wiring kit |
| current sensor type | B type closed toroid |
| [Ie] rated operational current | 80 A |
| Network frequency | 50/60 Hz, 0...2000 Hz |
|---|---|
| [Icw] rated short-time withstand current | 25 kA for 0.5 s |
| Residual short-circuit withstand current | 36 kA / 0.5 s conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 800 V |
| Overvoltage category | III |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Mounting mode | Fixed (plain backplate), Fixed (DIN rail) |
| Connections - terminals | Prefabricated connection |
| Diameter | 35 mm inner: |
| Net weight | 0.390 kg |
| Height | 130 mm |
| Width | 97 mm |
| Depth | 61 mm |
| IP degree of protection | Body: IP40, Connectors: IP20 |
|---|---|
| Environmental characteristic | Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56, Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30, Salt mist: Kb/2 conforming to IEC 60068-2-52 |
| Pollution degree | Level 2 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -25…70 °C |
| Standards | IEC 60947-2 |
| Product certifications | CE |
| Part number | LV481015 |
|---|---|
| Type designation | TB35P |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.0 cm |
| Package 1 Width | 12.0 cm |
| Package 1 Length | 16.0 cm |
| Package 1 Weight | 436.0 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 30 cm |
| Package 2 Width | 40 cm |
| Package 2 Length | 60 cm |
| Package 2 Weight | 5.036 kg |
| Shipping weight | 0.39 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for TB35P is 85389099.
TB35P ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare 1600-2500A ACB platforms: ABB Emax 2, Schneider MTZ2, Siemens 3WL2 on breaking capacity, trip units, endurance and lifecycle cost. Shop at Stoklink.
ABB Emax 2 air circuit breaker selection, sizing, trip units, selectivity, and maintenance guide for 630 to 6300 A LV switchgear engineers. Shop at...
ABB air circuit breakers from 630A to 1600A: selection criteria, IEC 60947-2 compliance, installation best practices, and maintenance tips. Shop at Stoklink.