The Schneider Electric LU6MB0BL is a TeSys U reverser block for side mounting, rated 38 A at 690 V with a 24 V DC coil, adding reversing contacts and interlocking to an advanced LUB120, LUB320, or LUB380 power base fitted with a LUC*BL control unit. Combined with an LU9MR1 assembling connector and LU9M1 terminal block, it completes a side-mounted reversing starter-controller.
The LU6MB0BL extends the side-mounted reverser block range to 38 A and to the LUB380 base, which the lower-current LU6MB0B does not cover. Its 24 V DC coil draws only 120 mA holding current against 2360 mA for the AC-coil LU6MB0B, a relevant difference when sizing the upstream control relay. Choose the vertical LU2MB0BL instead where panel depth favors vertical stacking over side mounting.
| Range | TeSys |
|---|---|
| Device short name | LU6MB |
| Product or Component Type | Reverser block |
| Device mounting | Separate mounting |
| Device Application | Motor control |
| [Ie] rated operational current | 38 A |
| [Uc] control circuit voltage | 24 V DC |
| Current consumption | 120 mA 24 V DC I maximum while closing, 120 mA 24 V DC I rms sealed |
| [Ue] rated operational voltage | 690 V AC power circuit |
|---|---|
| Network frequency | 40...60 Hz |
| Inrush restraint duration | 25 ms AC, 15 ms DC |
| Operating time | 150 ms with change of direction, 75 ms without change of direction |
| Standards | EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, with phase barrier, CSA C22.2 No 60947-4-1, with phase barrier |
| Product Certifications | CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine |
| [Ui] rated insulation voltage | 690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kVIEC 60947-6-2 |
| Fixing mode | Clipped (DIN rail), Screw-fixed (plate) |
| Connections - terminals | Control circuit screw clamp terminals 1 0.0005…0.002 in² (0.34…1.5 mm²) 0.1 in (3 mm)) flexible with cable end, Control circuit screw clamp terminals 1 0.001…0.002 in² (0.75…1.5 mm²) 0.1 in (3 mm)) flexible without cable end, Control circuit screw clamp terminals 1 0.001…0.002 in² (0.75…1.5 mm²) 0.1 in (3 mm)) rigid, Control circuit screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²) 0.1 in (3 mm)) flexible with cable end, Control circuit screw clamp terminals 2 0.001…0.002 in² (0.75…1.5 mm²) 0.1 in (3 mm)) flexible without cable end, Control circuit screw clamp terminals 2 0.001…0.002 in² (0.75…1.5 mm²) 0.1 in (3 mm)) rigid, Power circuit screw clamp terminals 1 0.002…0.02 in² (1…10 mm²) 0.2 in (4 mm)) rigid, Power circuit screw clamp terminals 1 0.002…0.009 in² (1…6 mm²) 0.2 in (4 mm)) flexible with cable end, Power circuit screw clamp terminals 1 0.004…0.02 in² (2.5…10 mm²) 0.2 in (4 mm)) flexible without cable end, Power circuit screw clamp terminals 2 0.002…0.009 in² (1…6 mm²) 0.2 in (4 mm)) flexible with cable end, Power circuit screw clamp terminals 2 0.002…0.009 in² (1…6 mm²) 0.2 in (4 mm)) rigid, Power circuit screw clamp terminals 2 0.002…0.009 in² (1.5…6 mm²) 0.2 in (4 mm)) flexible without cable end |
| Tightening torque | Control circuit: 7.08…10.6 lbf.in (0.8…1.2 N.m) flat screwdriver 0.2 in (5 mm), Control circuit: 7.08…10.6 lbf.in (0.8…1.2 N.m) Philips No 2 screwdriver 0.2 in (5 mm), Power circuit: 16.8…22.1 lbf.in (1.9…2.5 N.m) flat screwdriver 0.2 in (6 mm), Power circuit: 16.8…22.1 lbf.in (1.9…2.5 N.m) Philips No 2 screwdriver 0.2 in (6 mm), Power circuit: 16.8…22.1 lbf.in (1.9…2.5 N.m) pozidriv No 2 screwdriver 0.2 in (6 mm) |
| Width | 1.8 in (45 mm) |
| Height | 4.5 in (115 mm) |
| Depth | 4.4 in (113 mm) |
| Net Weight | 0.937 lb(US) (0.425 kg) |
| Compatibility code | LU6MB |
| IP degree of protection | IP20 IEC 60947-1 front panel and wired terminals), IP20 IEC 60947-1 other faces), IP40 IEC 60947-1 front panel outside connection zone) |
|---|---|
| Protective treatment | TH IEC 60068 |
| Ambient air temperature for operation | -13…140 °F (-25…60 °C) with LUCM, -13…158 °F (-25…70 °C) with LUCA, LUCB, LUCC, LUCD |
| Ambient air temperature for storage | -40…185 °F (-40…85 °C) |
| Fire resistance | 1760 °F (960 °C) parts supporting live components IEC 60695-2-12, 1202 °F (650 °C) IEC 60695-2-12 |
| Operating altitude | 6561.68 ft (2000 m) |
| Shock resistance | 10 gn power poles open IEC 60068-2-27, 15 gn power poles closed IEC 60068-2-27 |
| Vibration resistance | 2 gn 5…300 Hz) power poles open IEC 60068-2-27, 4 gn 5…300 Hz) power poles closed IEC 60068-2-27 |
| Resistance to electrostatic discharge | 8 kV level 3, in open air IEC 61000-4-2, 8 kV level 4, on contact IEC 61000-4-2 |
| Resistance to radiated fields | 9.1 V/m (10 V/m) level 3 IEC 61000-4-3 |
| Resistance to fast transients | 2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4 |
| Immunity to radioelectric fields | 10 V IEC 61000-4-6 |
| Part number | LU6MB0BL |
|---|---|
| Type designation | LU6MB |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389110106183 |
| Warranty (in months) | 18 |
|---|
| Country of origin | FR |
|---|---|
| Shipping weight | 0.425 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LU6MB is 38 A.
The tariff (HS) code on file for LU6MB is 853650.
The EAN (GTIN) of LU6MB is 3389110106183.
LU6MB ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Size a contactor for a 3-phase motor using IEC 60947-4-1 methodology, AC-3 vs AC-4 categories, NEMA equivalents, and Type 2 coordination. Shop at Stoklink.