Contactors for Data Center PDU and UPS Systems: Selection Guide
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
The Schneider Electric LC1D80ED is a 3-pole TeSys Deca Advanced contactor rated 80 A (AC-3) / 37 kW at 400 V, 60 hp at 480 V, with a 48 V DC coil and 1 NO + 1 NC auxiliary contacts.
The Schneider Electric LC1D80ED is a 3-pole TeSys Deca contactor rated 80 A AC-3 at up to 440 V, switching motors up to 37 kW at 400 V. It ships with a 48 V DC coil carrying a built-in transient suppressor module and a 1 NO + 1 NC auxiliary block with a mirror-certified NC contact.
The 48 V DC coil with built-in transient suppressor module suits panels powered from a DC control bus or battery backup rather than a transformer tap, and it lengthens the frame depth to 186 mm versus the AC-coil version at this current rating. Pick this DC-coil variant when the control architecture is already 48 V DC; choose an AC-coil sibling in the LC1D range when the panel runs on a standard AC control transformer instead.
Motor starters up to 37 kW at 400 V in DC-control panels, battery-backed control systems, and installations where 48 V DC logic already drives other field devices.
Applications (manufacturer): Motor control, Resistive load
| Series | TeSys Deca Advanced |
|---|---|
| Contactor size / frame | D80 |
| Number of poles | 3 |
| Main contact configuration | 3 NO |
| Utilisation categories | AC-3 AC-3e AC-1 AC-4 |
| Rated operational current Ie, AC-3, 400 V | 80 A |
|---|---|
| Rated motor power, AC-3, 400 V | 37 kW |
| Motor power at other voltages, AC-3 | 22 kW @ 220/230 V · 45 kW @ 415/440 V · 55 kW @ 500 V · 45 kW @ 660/690 V · 45 kW @ 1000 V |
| Rated operational current, AC-1 (60 °C) | 125 A |
| Conventional free-air thermal current Ith | 125 A |
| Rated motor power, AC-4, 400 V | 15 kW |
| Max. rated operational voltage Ue | 1000 V |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8 kV |
| Rated control supply voltage Uc | 48 V |
|---|---|
| Coil type | DC |
| Coil technology | Without built-in suppressor module |
| Coil holding power | 22 W | VA |
| Part number | LC1D80ED |
|---|---|
| Model code | D80 |
| Brand | Schneider Electric |
| Series | TeSys Deca Advanced |
| Family | Contactors |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389110440331 |
| Catalogue number explained | LC1 = 3-pole contactor; D = TeSys Deca Advanced range; 80 = 80 A AC-3 rating; ED = coil code (48 V DC) |
| Built-in auxiliary contacts, NO | 1 |
|---|---|
| Built-in auxiliary contacts, NC | 1 |
| Auxiliary contacts | 1 NO + 1 NC |
| Mirror contact (IEC 60947-4-1 Annex F) | Yes |
| Main circuit connection | Box lug / connector |
|---|---|
| Mounting | 35 mm DIN rail, Panel (screw) mounting |
| Width | 85 mm |
|---|---|
| Height | 127 mm |
| Depth | 186 mm |
| Net weight | 2.59 kg |
| Ambient operating temperature | -40 … 60 °C |
|---|---|
| Degree of protection | IP20 |
| Mechanical durability | 4000000 cycles |
| Max. operating frequency, AC-3 | 3600 cycles/h |
| Motor rating (UL/CSA) | 30 hp @ 200/208 V · 30 hp @ 230/240 V · 60 hp @ 460/480 V · 60 hp @ 575/600 V · 7.5 hp @ 120 V (1-ph) · 15 hp @ 230/240 V (1-ph) |
|---|---|
| Short-circuit current rating (SCCR) | 100 kA |
| Max. operating voltage UL/CSA | 600 V |
| Certifications | CB Scheme, UL, CSA, CCC, CE, UKCA, EAC, Marine |
|---|---|
| Conforming standards | CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60335-2-40, IEC 60947-4-1, IEC 60947-5-1, UL 60335-2-40, UL 60947-4-1 |
| Package dimensions (L × W × H) | 158 × 216 × 110 mm |
|---|---|
| Package weight | 2.602 kg |
| Shipping weight | 2.59 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
| Range | TeSys |
|---|---|
| Product or Component Type | Contactor |
| Device short name | LC1D |
| Compatibility code | LC1D |
| Protective cover | With |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 1100 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit 135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 200 A gG at <= 690 V coordination type 1 for power circuit 160 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 5.1 W AC-3 12.5 W AC-1 5.1 W AC-3e |
| Overvoltage category | III |
| Pollution degree | 3 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Electrical durability | 0.8 Mcycles 125 A AC-1 <= 440 V 1.5 Mcycles 80 A AC-3 <= 440 V 1.5 Mcycles 80 A AC-3e <= 440 V |
| Control circuit type | DC standard |
| Control circuit voltage limits | 0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational DC 1...1.1 Uc (131...158 °F (55...70 °C)):operational DC |
| Inrush power in W | 22 W 68 °F (20 °C)) |
| Operating time | 95...130 ms closing 20...35 ms opening |
| Time constant | 75 ms |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm) Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Protective treatment | THIEC 60068-2-30 |
| Climatic withstand | IACS E10 exposure to damp heat |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor closed 10 Gn for 11 ms) |
| Category | US1CTR121252 |
| Discount Schedule | CTR1 |
| Returnability | No |
| Unit Type of Package 1 | PCE |
| Nbr. of units in pkg. | 1 |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 5.9 in (15 cm) |
| Package 2 Width | 11.8 in (30 cm) |
| Package 2 Length | 15.7 in (40 cm) |
| Package 2 Weight | 12.066 lb(US) (5.473 kg) |
| Total lifecycle Carbon footprint | 176 kg CO2 eq. |
| Carbon footprint of the manufacturing phase [A1 to A3] | 17 kg CO2 eq. |
| Carbon footprint of the distribution phase [A4] | 0.3 kg CO2 eq. |
| Carbon footprint of the installation phase [A5] | 0.5 kg CO2 eq. |
| Carbon footprint of the use phase [B2, B3, B4, B6] | 151 kg CO2 eq. |
| Carbon footprint of the end-of-life phase [C1 to C4] | 6 kg CO2 eq. |
| Environmental Disclosure | Product Environmental Profile |
| Packaging made with recycled cardboard | Yes |
| Packaging without single use plastic | Yes |
| California proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer and/or birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov. |
| PVC free | Yes |
| Recyclability potential, in % | 76 |
| Circularity Profile | No need of specific recycling operations |
| Take-back | No |
| WEEE Label | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Source: manufacturer data · Last verified: 03 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LC1D80ED is 80 A (AC-3, 400 V).
The rated operational voltage of LC1D80ED is 1000 V AC.
The rated motor power of LC1D80ED is 37 kW (AC-3, 400 V).
The control voltage range of LC1D80ED is 48 V DC.
The EAN (GTIN) of LC1D80ED is 3389110440331.
LC1D80ED ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Master AC3 rating selection with our complete contactor checklist covering load sizing, utilization categories, derating, and coordination. Shop at Stoklink.