The Schneider Electric LC1D18M7 is a 3-pole TeSys Deca Advanced contactor rated 18 A (AC-3) / 7.5 kW at 400 V, 10 hp at 480 V, with a 220 V AC 50/60 Hz coil and 1 NO + 1 NC auxiliary contacts.
The Schneider Electric LC1D18M7 is a TeSys Deca series 3-pole AC contactor rated at 18A with a 10HP motor load capacity at 480V AC, designed for reliable motor switching and control applications in industrial environments. As a power contactor in the widely trusted TeSys Deca lineup, the LC1D18M7 delivers a 100kA SCCR (Short-Circuit Current Rating), making it suitable for demanding industrial power distribution panels. This contactor is an ideal solution for engineers and procurement professionals sourcing IEC-compliant motor starter contactor assemblies.
Applications (manufacturer): Resistive load, Motor control
| Series | TeSys Deca Advanced |
|---|---|
| Contactor size / frame | D18 |
| Number of poles | 3 |
| Main contact configuration | 3 NO |
| Utilisation categories | AC-3 AC-3e AC-1 AC-4 |
| Rated operational current Ie, AC-3, 400 V | 18 A |
|---|---|
| Rated motor power, AC-3, 400 V | 7.5 kW |
| Motor power at other voltages, AC-3 | 4 kW @ 220/230 V · 9 kW @ 415/440 V · 10 kW @ 500 V · 10 kW @ 660/690 V |
| Rated operational current, AC-1 (60 °C) | 32 A |
| Conventional free-air thermal current Ith | 32 A |
| Rated motor power, AC-4, 400 V | 4 kW |
| Max. rated operational voltage Ue | 690 V |
| Rated insulation voltage Ui | 690 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Rated control supply voltage Uc | 220 V |
|---|---|
| Coil type | AC |
| Coil frequency | 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Coil holding power | 7.5 W | VA |
| Part number | LC1D18M7 |
|---|---|
| Model code | D18 |
| Brand | Schneider Electric |
| Series | TeSys Deca Advanced |
| Family | Contactors |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389110349504 |
| Catalogue number explained | LC1 = 3-pole contactor; D = TeSys Deca Advanced range; 18 = 18 A AC-3 rating; M7 = coil code (220 V AC 50/60 Hz) |
| Built-in auxiliary contacts, NO | 1 |
|---|---|
| Built-in auxiliary contacts, NC | 1 |
| Auxiliary contacts | 1 NO + 1 NC |
| Mirror contact (IEC 60947-4-1 Annex F) | Yes |
| Main circuit connection | Screw terminal |
|---|---|
| Mounting | 35 mm DIN rail, Panel (screw) mounting |
| Width | 45 mm |
|---|---|
| Height | 77 mm |
| Depth | 86 mm |
| Net weight | 0.33 kg |
| Ambient operating temperature | -40 … 60 °C |
|---|---|
| Degree of protection | IP20 |
| Mechanical durability | 15000000 cycles |
| Max. operating frequency, AC-3 | 3600 cycles/h |
| Motor rating (UL/CSA) | 5 hp @ 200/208 V · 5 hp @ 230/240 V · 10 hp @ 460/480 V · 15 hp @ 575/600 V · 1 hp @ 115 V (1-ph) · 3 hp @ 230/240 V (1-ph) |
|---|---|
| Short-circuit current rating (SCCR) | 100 kA |
| Max. operating voltage UL/CSA | 600 V |
| Certifications | CB Scheme, UL, CSA, CCC, UKCA, EAC, Marine |
|---|---|
| Conforming standards | CSA C22.2 No 14, CSA C22.2 No 60947-4-1, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60335-2-40, IEC 60947-4-1, IEC 60947-5-1, UL 60335-2-40, UL 60947-4-1 |
| Package dimensions (L × W × H) | 120 × 100 × 55 mm |
|---|---|
| Package weight | 0.365 kg |
| Shipping weight | 0.33 kg |
| Ships from | Türkiye |
| Dispatch | 16 Nov |
| Stock | In stock |
| Product or Component Type | Contactor |
|---|---|
| Device short name | LC1D |
| Compatibility code | LC1D |
| Protective cover | With |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 300 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 145 A 104 °F (40 °C) - 10 s for power circuit 240 A 104 °F (40 °C) - 1 s for power circuit 40 A 104 °F (40 °C) - 10 min for power circuit 84 A 104 °F (40 °C) - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 50 A gG at <= 690 V coordination type 1 for power circuit 35 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
| Power dissipation per pole | 2.5 W AC-1 0.8 W AC-3 0.8 W AC-3e |
| Overvoltage category | III |
| Pollution degree | 3 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Electrical durability | 1.65 Mcycles 18 A AC-3 <= 440 V 1 Mcycles 32 A AC-1 <= 440 V 1.65 Mcycles 18 A AC-3e <= 440 V |
| Control circuit type | AC 50/60 Hz standard |
| Control circuit voltage limits | 0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...140 °F (-40...60 °C)):operational AC 50 Hz 0.85...1.1 Uc (-40...140 °F (-40...60 °C)):operational AC 60 Hz 1...1.1 Uc (140...158 °F (60...70 °C)):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C)) |
| Heat dissipation | 2...3 W at 50/60 Hz |
| Operating time | 12...22 ms closing 4...19 ms opening |
| Tightening torque | Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2 Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Protective treatment | THIEC 60068-2-30 |
| Climatic withstand | IACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms) |
| Category | US1CTR121251 |
| Discount Schedule | CTR1 |
| Returnability | Yes |
| Unit Type of Package 1 | PCE |
| Nbr. of units in pkg. | 1 |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 5.906 in (15.000 cm) |
| Package 2 Width | 11.811 in (30.000 cm) |
| Package 2 Length | 15.748 in (40.000 cm) |
| Package 2 Weight | 16.028 lb(US) (7.270 kg) |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 29.528 in (75.000 cm) |
| Package 3 Width | 23.622 in (60.000 cm) |
| Package 3 Length | 31.496 in (80.000 cm) |
| Package 3 Weight | 275.525 lb(US) (124.976 kg) |
| Total lifecycle Carbon footprint | 26 kg CO2 eq. |
| Carbon footprint of the manufacturing phase [A1 to A3] | 1 kg CO2 eq. |
| Carbon footprint of the distribution phase [A4] | 0.2 kg CO2 eq. |
| Carbon footprint of the installation phase [A5] | 0.1 kg CO2 eq. |
| Carbon footprint of the use phase [B2, B3, B4, B6] | 24 kg CO2 eq. |
| Environmental Disclosure | Product Environmental Profile |
| Packaging made with recycled cardboard | Yes |
| Packaging without single use plastic | Yes |
| California proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer and/or birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov. |
| PVC free | Yes |
| Recyclability potential, in % | 66 |
| Circularity Profile | End of Life Information |
| Take-back | No |
| WEEE Label | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Source: manufacturer data · Last verified: 03 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LC1D18M7 is 18 A (AC-3, 400 V).
The rated operational voltage of LC1D18M7 is 690 V AC.
The rated motor power of LC1D18M7 is 7.5 kW (AC-3, 400 V).
The control voltage range of LC1D18M7 is 220 V AC.
The EAN (GTIN) of LC1D18M7 is 3389110349504.
LC1D18M7 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1 business day.
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Master AC3 rating selection with our complete contactor checklist covering load sizing, utilization categories, derating, and coordination. Shop at Stoklink.