Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
The Schneider Electric G12UVR415AC is an MN undervoltage release fitted to the GoPact MCCB 125, wired to a 415 V AC 50/60 Hz control circuit. It opens the breaker once the supply voltage falls below 0.7 times Un, with opening guaranteed below 0.35 times Un, and holds the breaker closed above 0.85 times Un. Maximum response time is 25 ms.
Specify the G12UVR415AC when the GoPact MCCB 125 must open automatically on loss or sag of its 415 V AC control supply rather than relying on an operator - useful where downstream equipment must not re-energize unexpectedly after a dip. Because opening is only guaranteed below 0.35 times Un and merely possible up to 0.7 times Un, it is not a substitute for a shunt-trip release where a fast, voltage-independent remote-trip signal is required.
| Range of product | GoPact MCCB |
|---|---|
| Product or component type | Voltage release |
| Device short name | MN |
| Device application | Control |
| Range compatibility | GoPact MCCB 125 |
| Voltage release type | Undervoltage release |
| [Uc] control circuit voltage | 415 V AC 50/60 Hz |
| Threshold tripping voltage | 0.35...0.7 Un opening, 0.85...1.1 Un closing |
|---|---|
| Max supply holding power consumption | 3.5 VA |
| Max supply pick-up power consumption | 5 VA |
| Response time | 25 ms |
| Warranty (in months) | 18 |
|---|
| Part number | G12UVR415AC |
|---|---|
| Type designation | MN |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.5 cm |
| Package 1 Width | 8.5 cm |
| Package 1 Length | 4.8 cm |
| Package 1 Weight | 900 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 2.115 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 60 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 42.34 kg |
| Shipping weight | 0.9 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of MN is 415 V AC.
The tariff (HS) code on file for MN is 853890.
MN ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...