Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Schneider Electric E080F320FM, EasyPact CVS800F, 3P 800 A, 36 kA at 380/415 V AC, ETS 2.0 electronic trip
The Schneider Electric E080F320FM is a 800 A EasyPact CVS800F moulded case circuit breaker for low-voltage electrical distribution, built on a standard-breaking F frame. Its ETS 2.0 electronic trip unit gives adjustable long-time overload and instantaneous short-circuit protection (LI), and the 3-pole, 3D frame breaks 36 kA at 380/415 V AC under IEC 60947-2.
Pick the F frame where available fault current stays under 36 kA at 380/415 V; it is the lightest-duty, lowest-cost frame in this CVS range. The 3-pole frame protects the three phase conductors only; use it on a balanced three-phase feeder where the neutral is bonded upstream or not distributed. Within the 800 A CVS800 frame size, E080F320FM (F class) sits alongside breaking-class siblings at the same amperage -- move up a class if downstream fault studies show higher prospective short-circuit current than 36 kA at 380/415 V, since the ETS 2.0 long-time setting only trims down to 0.4 x In (320 A) and cannot raise the frame's current rating.
| Range | EasyPact |
|---|---|
| Range of product | EasyPact CVS |
| Product or component type | Circuit breaker |
| Device short name | CVS800F |
| Device application | Low voltage electrical distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
|---|---|
| [In] rated current | 800 A at 50 °C |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-3 |
| Power dissipation | 15 W |
| Protection type | L : for overload protection (long time), I : for instantaneous short-circuit protection |
| Breaking capacity code | F 36 kA 415 V AC |
| Local signalling | 4 LEDs (red) for fault indication, 1 LED (yellow) for overload |
| Auxiliary contact composition | 1 NO/NC |
| Earth-leakage protection | Without |
| Control type | Rotary handle, Toggle |
| Breaking capacity | 50 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Utilisation category | Category A |
| [Ics] rated service breaking capacity | 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 5000 cycles |
| Electrical durability | 3000 cycles at 415 V In, 2000 cycles at 440 V In |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Connection pitch | 70 mm |
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Trip unit name | ETS 2.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LI |
| Trip unit rating | 800 A at 50 °C |
| Long time pick-up adjustment type Ir | Adjustable |
| Long time pick-up adjustment range | 0.4...1 x In |
| Long time delay adjustment type | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir, 0.5…24 s at 6 x Ir, 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Instantaneous pick-up adjustment type Ii | Adjustable |
| Instantaneous pick-up adjustment range | 1.5...10 x Ir |
| Zone selective interlocking ZSI | Without |
| Net weight | 14 kg |
| IP degree of protection | IP40 conforming to IEC 60529 |
|---|---|
| IK degree of protection | IK07 conforming to IEC 62262 |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000...5000 m with derating |
| Height | 327 mm |
| Width | 210 mm |
| Depth | 147 mm |
| Standards | EN/IEC 60947-2 |
| Product certifications | CCC, CB, CE |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Part number | E080F320FM |
|---|---|
| Type designation | CVS800F |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 30 cm |
| Package 1 Width | 40 cm |
| Package 1 Length | 60 cm |
| Package 1 Weight | 14.8 kg |
| Unit Type of Package 2 | P12 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 105 cm |
| Package 2 Width | 80 cm |
| Package 2 Length | 120 cm |
| Package 2 Weight | 130.9 kg |
| Shipping weight | 14.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of CVS800F is 800 A.
The rated operational voltage of CVS800F is 440 V AC.
The tariff (HS) code on file for CVS800F is 853620.
CVS800F ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...