Part number
C25W4TM200
Model no
NSX250HB2
4,682.83 SR On request Dispatch — · From TürkiyeGet a Quote

Schneider Electric C25W4TM200 ComPacT NSX250HB2 4P 200 A 100 kA TM-D Fixed Moulded Case Circuit Breaker

ComPacT NSX250HB2 MCCB, 4P 200 A, 100 kA at 690 V AC, TM-D trip unit.

Rated current
200 A
Rated operational voltage
690 V AC
Poles
4P
Description

About the NSX250HB2

The Schneider Electric C25W4TM200 is a 4-pole ComPacT NSX250HB2 moulded case circuit breaker rated 200 A on a TM-D thermal-magnetic trip unit, built on the HB2 690 V AC frame. Breaking capacity (Icu) is 100 kA across the 500 V, 525 V and 660/690 V AC classes, against a 690 V AC rated operational voltage, for the highest-fault-current 690 V applications in the NSX250 range.

Certifications & Standards

  • EN/IEC 60947-2

Selection Notes

At 100 kA Icu across the full 500-690 V AC band, the HB2 frame is the top breaking-capacity option in the NSX250 range and is the one to specify where prospective fault current at 690 V exceeds the HB1 frame's 75 kA rating. The 4th pole trips at 1 x Ir for a protected neutral on 4-wire 690 V feeders; Pick a different trip-current sibling in the same HB2 series to match load current without changing the breaking-capacity class.

Specification

Full specification

87 values · Last verified 30 Oct 2026

Main 21

Range ComPacT
Product name ComPacT NSX
Device short name NSX250HB2
Product or component type Circuit breaker
Device application Distribution
Poles description 4P
Protected poles description 4D
Neutral position Left
[In] rated current 200 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
Breaking capacity 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code HB2 100 kA 690 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed

Complementary 26

[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service breaking capacity 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles at 440 V In/2, 10000 cycles at 440 V In, 10000 cycles at 690 V In/2, 5000 cycles at 690 V In
Power dissipation per pole 15.4 W
Mounting support Backplate
Mounting position Horizontal and vertical, Flat on the back
Upside connection Front
Downside connection Front
Connection pitch 35 mm
Protection type L : for overload protection (thermal), I : for short-circuit protection (magnetic)
Trip unit rating 200 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
[tr] long-time delay adjustment range 120…400 s at 1.5 x In, 15 s at 6 x Ir
Neutral protection setting 1 x Ir (4D)
Instantaneous protection pick-up adjustment type Ii Adjustable
[Ii] instantaneous protection pick-up adjustment range 5...10 x In
Earth-leakage protection Without
Number of slots 5 slot(s)
Width (W) 140 mm
Height (H) 161 mm
Depth (D) 86 mm
Net weight 2.8 kg

Environment 10

Standards EN/IEC 60947-2
Overvoltage category III
Electrical shock protection class Class II on front face
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating, 2000 m...5000 m with derating
Show all 87 specifications ↓ Show less ↑30 more values in Identification, Contractual warranty, Logistics.

Identification 7

Part number C25W4TM200
Type designation NSX250HB2
Brand Schneider Electric
Condition New, factory sealed
Source Schneider Electric and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production

Contractual warranty 1

Warranty (in months) 18

Logistics 22

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 14.000 cm
Package 1 Width 15.000 cm
Package 1 Length 20.000 cm
Package 1 Weight 2.740 kg
Unit Type of Package 2 S03
Number of Units in Package 2 3
Package 2 Height 30.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 8.640 kg
Unit Type of Package 3 P12
Number of Units in Package 3 24
Package 3 Height 45.000 cm
Package 3 Width 80.000 cm
Package 3 Length 120.000 cm
Package 3 Weight 81.120 kg
Shipping weight 2.8 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 30 Oct 2026

Documents

Documents for C25W4TM200

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • EN/IEC 60947-2
Quick answers

Questions about the NSX250HB2

What is the rated current of NSX250HB2?

The rated current of NSX250HB2 is 200 A.

Which supply voltage is NSX250HB2 rated for?

The rated operational voltage of NSX250HB2 is 690 V AC.

What is the HS code of NSX250HB2 for customs?

The tariff (HS) code on file for NSX250HB2 is 85362090.

Where does NSX250HB2 ship from, and how fast?

NSX250HB2 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for MCCB

All guides for MCCB
Reviews

Customer reviews

Series

Schneider Electric Schneider ComPacT NSX

Brand
Schneider Electric
Series
Schneider ComPacT NSX
Series page →
Series

Other series in Molded Case Circuit Breakers (MCCB)

4,682.83 SR On request
Get a Quote
Quote

Get a Quote

NSX250HB2

Genuine parts

Genuine, factory-sealed parts

Schneider Electric · C25W4TM200

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Schneider Electric and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart