Schneider Electric C160H450FM – ComPacT NS1600H 4P 1600 A MCCB, 70 kA at 415 V AC, MicroLogic 5.0 trip unit.
The Schneider Electric C160H450FM is a 4-pole, 1600 A ComPacT NS1600H moulded case circuit breaker rated for a breaking capacity of 70 kA at 380/415 V AC. It carries a MicroLogic 5.0 electronic trip unit with long-time, short-time and instantaneous (LSI) protection and an operational voltage of 690 V AC, suited for fixed, manually-operated distribution boards up to 1600 A.
The MicroLogic 5.0 trip unit decodes to long-time overload (L), short-time delay (S) and instantaneous (I) protection, giving the C160H450FM adjustable short-time discrimination with downstream breakers in a 4-pole, 1600 A NS1600H frame. Zone selective interlocking is not available on this trip unit, so fault clearance relies on the Isd time-delay setting instead of a ZSI link. Choose this 5.0 (LSI) version over the 2.0 (LI) sibling when short-time coordination is required, or over 6.0 (LSIG) when ground-fault protection is not needed in this circuit.
| Range | ComPacT |
|---|---|
| Product name | ComPacT NS new generation |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4D |
| Neutral position | Left |
| [In] rated current | 1600 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category B |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H 70 kA 415 V AC |
| Trip unit name | MicroLogic 5.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSI |
| Control type | Manually operated |
| Mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Mechanical durability | 10000 cycles |
| Electrical durability | 1000 cycles at 690 V In, 2000 cycles at 690 V In/2, 2000 cycles at 440 V In, 5000 cycles at 440 V In/2 |
| Power losses | 74 W |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 70 mm |
| Protection type | L : for overload protection (long time), S : for short time short-circuit protection, I : for instantaneous short-circuit protection |
| Trip unit rating | 1600 A at 50 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir, 0.5…24 s at 6 x Ir, 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] short-time delay adjustment range | 0.1…0.4 s I²t=on, 0…0.4 s I²t=off |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | Off, 2...15 x In |
| Earth-leakage protection | Without |
| Neutral protection setting | No protection (3D), 0.5 x Ir (3D + N/2), 1 x Ir (4D) |
| Zone selective interlocking ZSI | Without |
| Auxiliary contact composition | 1 NO/NC |
| Local signalling | 4 LEDs (red) for fault indication, 1 LED (yellow) for overload |
| Width (W) | 280 mm |
| Height (H) | 327 mm |
| Depth (D) | 147 mm |
| Net weight | 18 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Product certifications | IECEE CB Scheme |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000 m...5000 m with derating |
| Part number | C160H450FM |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 37.0 cm |
| Package 1 Width | 38.0 cm |
| Package 1 Length | 30.0 cm |
| Package 1 Weight | 16.961 kg |
| Shipping weight | 18.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of C160H450FM is 1600 A.
The rated operational voltage of C160H450FM is 690 V AC.
The tariff (HS) code on file for C160H450FM is 85362090.
C160H450FM ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...