Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Schneider Electric C100N460FM ComPacT NS1000N 4P 1000 A, 50 kA Icu, MicroLogic 6.0 trip unit.
Schneider Electric's C100N460FM is a 4-pole, 1000 A ComPacT NS1000N moulded case circuit breaker with a 50 kA Icu rating at 380/415 V AC and a 690 V AC operational voltage. The fixed, front-connected breaker uses the MicroLogic 6.0 trip unit for overload (L), short-time delayed short-circuit (S), instantaneous (I) and ground-fault (G) protection.
The MicroLogic 6.0 trip unit on the C100N460FM is configured for overload (L), short-time delayed short-circuit (S), instantaneous (I) and ground-fault (G) protection. Stacking G (ground-fault) on top of L-S-I gives this trip unit adjustable earth-fault tripping as well as time-graded short-circuit discrimination, useful on solidly grounded systems that would otherwise need a separate earth-fault relay. In the NS1000 case size, this N-frame breaker is the standard breaking capacity option (50 kA Icu at 380/415 V AC); the H-frame (70 kA Icu) and the L-frame (150 kA Icu) versions share the same case and accessories but trade breaking capacity for cost or vice versa. The A- and E-suffix trip units in the same frame add an ammeter or energy meter respectively, for installations that want local metering without extra hardware. As a 4-pole unit it supports neutral protection options (no protection, half-rated N/2, or full-rated 4D) rather than the fixed 3-pole configuration.
| Range | ComPacT |
|---|---|
| Product name | ComPacT NS new generation |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4D |
| Neutral position | Left |
| [In] rated current | 1000 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category B |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | N 50 kA 415 V AC |
| Trip unit name | MicroLogic 6.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSIG |
| Control type | Manually operated |
| Mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Mechanical durability | 10000 cycles |
| Electrical durability | 2000 cycles at 690 V In, 4000 cycles at 690 V In/2, 5000 cycles at 440 V In, 6000 cycles at 440 V In/2 |
| Power losses | 22 W |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 70 mm |
| Protection type | L : for overload protection (long time), S : for short time short-circuit protection, I : for instantaneous short-circuit protection, G : for ground fault protection |
| Trip unit rating | 1000 A at 50 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir, 0.5…24 s at 6 x Ir, 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Adjustable |
| [tsd] short-time delay adjustment range | 0.1…0.4 s I²t=on, 0…0.4 s I²t=off |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | Off, 2...15 x In |
| Ground-fault protection pick-up adjustment type Ig | Adjustable 9 settings |
| [Ig] ground-fault pick-up adjustment range | 0.3...1 x In for In <= 400 A, 0.2...1 x In for 400 A < In < 1250 A, 500...1200 A for In >= 1250 A |
| Ground-fault protection time delay adjustment type tg | Adjustable |
| [tg] Ground-fault time delay adjustment range | 0.1…0.4 s I²t=on, 0…0.4 s I²t=off |
| Earth-leakage protection | Without |
| Neutral protection setting | No protection (3D), 0.5 x Ir (3D + N/2), 1 x Ir (4D) |
| Zone selective interlocking ZSI | Without |
| Auxiliary contact composition | 1 NO/NC |
| Local signalling | 4 LEDs (red) for fault indication, 1 LED (yellow) for overload |
| Width (W) | 280 mm |
| Height (H) | 327 mm |
| Depth (D) | 147 mm |
| Net weight | 18 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Product certifications | IECEE CB Scheme |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000 m...5000 m with derating |
| Part number | C100N460FM |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 37.0 cm |
| Package 1 Width | 38.0 cm |
| Package 1 Length | 30.0 cm |
| Package 1 Weight | 15.894 kg |
| Shipping weight | 18.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of C100N460FM is 1000 A.
The rated operational voltage of C100N460FM is 690 V AC.
The tariff (HS) code on file for C100N460FM is 853620.
C100N460FM ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...