Types of Molded Case Circuit Breakers: MCCB Guide for Engineers
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
C080L320FM – ComPacT NS800L 3P 800 A, 150 kA Icu at 380/415 V MCCB.
The Schneider Electric C080L320FM is a 3-pole ComPacT NS800L moulded case circuit breaker rated 800 A, with a 150 kA breaking capacity (Icu) at 380/415 V AC. It is fitted with a MicroLogic 2.0 trip unit delivering long-time overload and instantaneous short-circuit protection (LI), is fixed-mounted and manually operated, and carries a 690 V rated operational voltage for industrial distribution switchboards.
Its LI trip unit covers long-time overload and instantaneous short-circuit tripping only, which keeps the breaker simple and is adequate where upstream or downstream devices already handle short-time discrimination. The L-frame rating gives it 150 kA Icu at 380/415 V AC, the highest breaking-capacity class in the 800 A frame; reserve it for incomers close to the transformer or otherwise exposed to prospective fault currents above what the H-frame sibling can clear.
| Range | ComPacT |
|---|---|
| Product name | ComPacT NS new generation |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Number of poles | 3P |
| Protected poles description | 3D |
| [In] rated current | 800 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | L 150 kA 415 V AC |
| Trip unit name | MicroLogic 2.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LI |
| Control type | Manually operated |
| Mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Mechanical durability | 10000 cycles |
| Electrical durability | 2000 cycles at 690 V In, 3000 cycles at 690 V In/2, 3000 cycles at 440 V In, 4000 cycles at 440 V In/2 |
| Power losses | 20 W |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 70 mm |
| Protection type | L : for overload protection (long time), I : for instantaneous short-circuit protection |
| Trip unit rating | 800 A at 50 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir, 0.5…24 s at 6 x Ir, 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
| Earth-leakage protection | Without |
| Zone selective interlocking ZSI | Without |
| Auxiliary contact composition | 1 NO/NC |
| Local signalling | 4 LEDs (red) for fault indication, 1 LED (yellow) for overload |
| Width (W) | 210 mm |
| Height (H) | 327 mm |
| Depth (D) | 147 mm |
| Net weight | 14 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Product certifications | IECEE CB Scheme |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating, 2000 m...5000 m with derating |
| Part number | C080L320FM |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 37.000 cm |
| Package 1 Width | 39.000 cm |
| Package 1 Length | 23.000 cm |
| Package 1 Weight | 13.227 kg |
| Shipping weight | 14.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of C080L320FM is 800 A.
The rated operational voltage of C080L320FM is 690 V AC.
The tariff (HS) code on file for C080L320FM is 85362090.
C080L320FM ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...