VFD for Compressors: Selection Guide
How to select and size a VFD for screw, reciprocating and centrifugal compressors, covering overload rating, turndown limits and energy savings.
Schneider Electric ATV610C16N4 Easy Altivar 610 ATV610 VFD, 160 kW normal duty, 380-460V 3-phase, IP00, cabinet mount.
The Schneider Electric ATV610C16N4 is an Altivar ATV610 variable speed drive for fan, pump, compressor and conveyor applications, rated 160 kW normal duty and 132 kW heavy duty. It runs from a 380-460 V three-phase supply, delivers 302 A continuous output current in normal duty, and mounts in a cabinet as an IP00 chassis. An integrated EMC filter meets IEC 61800-3 category C3.
The ATV610C16N4's normal-duty rating (160 kW, 302 A continuous) is the drive's marketed size, sharing the 300 x 375 mm footprint and 85.5 kg weight with the two power steps below it. Switch to heavy duty (132 kW, 250 A continuous, 375 A/60 s transient) for constant-torque conveyor or hoist loads that need deeper start-up overload margin rather than the higher continuous current. Line-side conductors up to 2 x 95...3 x 120 mm2 handle the 284 A line current at 380 V in normal duty.
| Range of product | Altivar ATV610 |
|---|---|
| Product specific application | Fan, pump, compressor, conveyor |
| Product or component type | Variable speed drive |
| Device short name | ATV610 |
| Variant | Standard version |
| Product destination | Asynchronous motors, Synchronous motors |
| Mounting mode | Cabinet mount |
| EMC filter | Integrated conforming to IEC 61800-3 category C3 with 50 m |
| IP degree of protection | IP00 |
| Type of cooling | Forced convection |
| Supply frequency | 50...60 Hz +/-5 % |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 380...460 V - 15...10 % |
| Motor power kW | 160 kW for normal duty, 132 kW for heavy duty |
| Motor power hp | 250 hp for normal duty, 200 hp for heavy duty |
| Line current | 284 A at 380 V (normal duty), 249.5 A at 460 V (normal duty), 237 A at 380 V (heavy duty), 205.9 A at 460 V (heavy duty) |
| Prospective line Isc | 50 kA |
| Apparent power | 198.8 kVA at 460 V (normal duty), 164.0 kVA at 460 V (heavy duty) |
| Continuous output current | 302 A at 2.5 kHz for normal duty, 250 A at 2.5 kHz for heavy duty |
| Maximum transient current | 332 A during 60 s (normal duty), 375 A during 60 s (heavy duty) |
| Asynchronous motor control profile | Constant torque standard, Optimized torque mode, Variable torque standard |
| Output frequency | 0.1…500 Hz |
| Nominal switching frequency | 2.5 kHz |
| Switching frequency | 1...8 kHz adjustable |
| number of preset speeds | 16 preset speeds |
| Communication port protocol | Modbus serial |
| Option card | Slot A: communication card, Profibus DP V1, Slot A: digital or analog I/O extension card, Slot A: relay output card |
| Output voltage | <= power supply voltage |
|---|---|
| Motor slip compensation | Not available in permanent magnet motor law, Automatic whatever the load, Adjustable, Can be suppressed |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 s, S, U or customized |
| Braking to standstill | By DC injection |
| Protection type | Thermal protection: motor, Motor phase break: motor, Thermal protection: drive, Overheating: drive, Overcurrent between output phases and earth: drive, Overload of output voltage: drive, Short-circuit protection: drive, Motor phase break: drive, Overvoltages on the DC bus: drive, Line supply overvoltage: drive, Line supply undervoltage: drive, Line supply phase loss: drive, Overspeed: drive, Break on the control circuit: drive |
| Frequency resolution | Display unit: 0.1 Hz, Analog input: 0.012/50 Hz |
| Electrical connection | Control, screw terminal: 0.5...1.5 mm², Line side, screw terminal: 2 x 95...3 x 120 mm², Motor, screw terminal: 2 x 95...3 x 120 mm² |
| Connector type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
| Physical interface | 2-wire RS 485 for Modbus serial |
| Transmission frame | RTU for Modbus serial |
| Transmission rate | 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
| Type of polarization | No impedance for Modbus serial |
| Number of addresses | 1…247 for Modbus serial |
| Method of access | Slave |
| Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection, Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
| Local signalling | 2 LEDs for local diagnostic, 1 LED (yellow) for embedded communication status, 2 LEDs (dual colour) for communication module status, 1 LED (red) for presence of voltage |
| Width | 300 mm |
| Depth | 375 mm |
| Net weight | 85.5 kg |
| Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits, AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits, AI2, AI3 software-configurable temperature probe or water level sensor |
| Discrete input number | 6 |
| Discrete input type | DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm, DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
| Input compatibility | DI1...DI6: logic input level 1 PLC conforming to IEC 61131-2, DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68 |
| Discrete input logic | Positive logic (source): DI1...DI6 configurable logic input, 11 V (state 1), Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1), Positive logic (source): DI5, DI6 configurable pulse input, 2.5 V (state 1) |
| Analogue output number | 2 |
| Analogue output type | Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits, Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Sampling duration | 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input, 2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input, 5 ms +/- 1 ms (DI5, DI6)configurable - pulse input, 10 ms +/- 1 ms (AQ1, AQ2) - analog output |
| Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input, +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |
| Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input, AQ1, AQ2: +/- 0.2 % for analog output |
| Relay output number | 3 |
| Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles, Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles, Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
| Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC, Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC, Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC, Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
| Isolation | Between power and control terminals |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
| Noise level | 76 dB conforming to 86/188/EEC |
|---|---|
| Power dissipation in W | 3270 W(forced convection) at 380 V, switching frequency 2.5 kHz |
| Operating position | Vertical +/- 10 degree |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2, Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3, Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5, Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6, 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 6 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -15…45 °C (without derating), 45…60 °C (with derating factor) |
| Operating altitude | <= 1000 m without derating, 1000...4800 m with current derating 1 % per 100 m |
| Environmental characteristic | Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3, Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 |
| Standards | IEC 61800-3, Environment 2 category C3 IEC 61800-3, IEC 61800-5-1, IEC 60721-3 |
| Marking | CE |
| Part number | ATV610C16N4 |
|---|---|
| Type designation | ATV610 |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 48.000 cm |
| Package 1 Width | 65.000 cm |
| Package 1 Length | 103.000 cm |
| Package 1 Weight | 97.461 kg |
| Shipping weight | 85.5 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of ATV610 is 302 A.
The rated operational voltage of ATV610 is 380–460 V AC.
The rated motor power of ATV610 is 160 kW.
The tariff (HS) code on file for ATV610 is 850440.
ATV610 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
How to select and size a VFD for screw, reciprocating and centrifugal compressors, covering overload rating, turndown limits and energy savings.
Size your VFD correctly with our complete guide covering FLA calculation, duty cycle, derating, harmonics, and brand-specific sizing tables. Shop at Stoklink.
Compare VFD types including VSI, CSI, PWM, and matrix converters with selection criteria, harmonic data, and real installation examples. Shop at Stoklink.