Part number
ATS130N2D73LT
Model no
ATS130
4,559.52 SR Low stock Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye

ATS130N2D73LT, ATS130 Series Soft Starter, 37 kW, 73 A, 380 to 415V AC

Rated current
73 A
Rated operational voltage
380–415 V AC
Motor power
37 kW
Control voltage
24 V
Poles
3P
Display
No
EAN
3606486007426
Description

About the ATS130

Schneider Electric ATS130 Soft Starter Series – Overview

Schneider Electric ATS130 soft starters are compact and modern motor starting solutions designed for efficient and reliable starting of asynchronous motors in industrial and commercial applications. The ATS130 series focuses on simplifying installation, reducing mechanical stress during motor start-up, and limiting inrush current while providing essential motor protection functions. With a space-saving design and intuitive configuration, ATS130 soft starters are well suited for pumps, fans, compressors, conveyors, and general-purpose machinery where compact motor control solutions are required.


Product Description: ATS130N2D73LT

The Schneider ATS130N2D73LT is a compact in-line soft starter rated for 73 A (rated operational current) and designed for three‑phase supplies from 200 to 480 V AC (50–60 Hz). Verified motor power compatibility for this SKU is 22 kW at 230 V, 37 kW at 400 V, and 45 kW at 440 V, making it suitable for medium‑to‑large asynchronous motors commonly used in pumps, fans, compressors and conveyors. This unit is supplied with a 24 V DC control circuit and provides essential start/stop control including boost and deceleration voltage ramp functions to reduce mechanical stress and limit inrush current. The ATS130N2D73LT includes an internal bypass, a relay output (R1A/R1C NO), LED status indicators and discrete PLC‑compatible inputs, and is built for panel or DIN‑rail mounting with an IP20 degree of protection. With a 10 cycles/hour rating and standard protections such as phase failure and starter thermal monitoring, this model is suited for simple machine control and applications where a compact, protection‑rich motor soft starter is required.

Specification

Full specification

86 values · Last verified 30 Oct 2026

Main 15

Range of Product Altivar Soft Starter ATS130
Product or Component Type Soft starter
Product destination Asynchronous motors
Product Specific Application Simple machine
Device short name ATS130
Phase 3 phase
Utilisation category AC-53A
Ue power supply voltage 200...480 V - 15...10 %
power supply frequency 50...60 Hz +/- 5 Hz
[Ie] rated operational current 73 A in line 104 °F (40 °C))
Service factor at Ie 100
Torque control False
IP Degree of Protection IP20
Motor power kW 22 kW 230 V normal duty, 37 kW 400 V normal duty, 45 kW 440 V normal duty
Maximum Horse Power Rating 20 hp 200 V normal duty, 20 hp 208 V normal duty, 25 hp 230 V normal duty, 50 hp 460 V normal duty, 50 hp 480 V normal duty

Complementary 38

Overload current profile 300 % Ie for 5 s
On-load factor 70 %
Operating cycles/hour 10 cyc/h
Minimum motor current 20 % Ie
Device connection In line
[Us] control circuit voltage 24 V DC +/- 10 %
Control power 21.6 W starting and stopping, 3 W steady state
Integrated motor overload protection False
Protection type Phase failure mains, Thermal protection starter, Bypass error starter, Control voltage Us starter
[In] Rated current pwr loss specifctn 73 A
Power loss static current independent 3 W
Power loss per device current dependent 20 W
Power loss during starting 454 W 300 % Ie
Standards EN/IEC 60947-4-2, UL 60947-4-2, IEC 60664-1
Product Certifications CE, UKCA, CCC, RCM, EAC, UL
Marking CE, CCC, UKCA, RCM, EAC
[Uc] control circuit voltage 24 V DC
Discrete input number 3
Discrete input type DI) digital input, 10 kOhm, DI2) digital input, 10 kOhm, BOOST) digital input, 10 kOhm
Input compatibility discrete input level 1 PLC EN/IEC 61131-2
Discrete input logic Digital input 0... 13 V, >= 0.5 mA
Relay output number 1
Relay output type Relay outputs R1A, R1C NO
Minimum switching current 2.5 mA 24 V DC relay outputs
Maximum switching current On resistive load for relay outputs : 1 A 250 V AC 400000 cycles, On resistive load for relay outputs : 1 A 30 V DC 400000 cycles, On inductive load for relay outputs : 1 A 250 V AC cos phi = 0.4 100000 cycles, On inductive load for relay outputs : 1 A 30 V DC cos phi = 0.4 100000 cycles
Discrete output number 1
Discrete output type Non programmable digital output DQ1 <= 30 V 200 mA
Display type 1 LED Green)control power energized, 1 LED yellow and red)motor operation phases, errors
Display screen available False
Operating position Vertical +/- 30 degree
Height 6.5 in (166 mm)
Width 2.2 in (55 mm)
Depth 6.5 in (165 mm)
Net Weight 2.9 lb(US) (1.3 kg)
Suitable for mounting onto standard rails True
Function Available Deceleration voltage ramp, Boost
internal bypass True
material declaration True

Environment 19

Pollution degree Level 2
environmental class (during operation) Without salt mist 3C3 IEC 60721-3-3, 3S3 IEC 60721-3-3
[Uimp] rated impulse withstand voltage 4 kV
[Ui] Rated Insulation Voltage 480 V
Electromagnetic compatibility Conducted and radiated emissions level B conforming to IEC 60947-4-2, Short voltage interruptions level 3 conforming to IEC 61000-4-11, Electrostatic discharge level 2 conforming to IEC 61000-4-2, Radiated radio-frequency electromagnetic field immunity test level 1 conforming to IEC 61000-4-3, Electrical fast transient/burst immunity test level 2 conforming to IEC 61000-4-4, Oscillatory waves immunity level 3 conforming to IEC 61000-4-12, Voltage/current impulse level 2 conforming to IEC 61000-4-5, Conducted disturbances, induced by radiofrequency fields level 1 conforming to IEC 61000-4-6
Ambient air temperature for operation 14…104 °F (-10…40 °C) (without derating), 104…140 °F (40…60 °C) (with current derating 1.5 % per °C)
Ambient Air Temperature for Storage -13…158 °F (-25…70 °C)
Ambient air transport temperature -40…158 °F (-40…70 °C)
Operating altitude 0...3280.84 ft (0...1000 m) without derating, 3280.84...13123.36 ft (1000...4000 m) 1 % per 100 m
Relative humidity 5…95 % non condensing without dripping water IEC 60068-2-3
Maximum acceleration under vibrational stress (during operation) 10 m/s² at 9...200 Hz
Maximum acceleration under vibratory load (during storage) 10 m/s² at 9...200 Hz
Maximum acceleration under vibratory load (during transport) 10 m/s² at 9...200 Hz
Maximum deflection under vibratory load (during operation) 3 mm at 2-9 Hz
Maximum deflection under vibratory load (during storage) 3 mm at 2-9 Hz
Maximum deflection under vibratory load (during transport) 3 mm at 2-9 Hz
Maximum acceleration under shock impact (during operation) 100 m/s² at 11 ms
Maximum acceleration under shock load (during storage) 100 m/s² at 11 ms
Maximum acceleration under shock load (during transport) 100 m/s² at 11 ms
Show all 86 specifications ↓ Show less ↑14 more values in Identification, Contractual warranty, Logistics.

Identification 8

Part number ATS130N2D73LT
Type designation ATS130
Brand Schneider Electric
Condition New, factory sealed
Source Schneider Electric and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 3606486007426

Contractual warranty 1

Warranty (in months) 18

Logistics 5

Country of origin DE
Shipping weight 1.3 kg
Ships from Türkiye
Dispatch 16 Nov
Stock Low stock

Source: manufacturer data · Last verified: 30 Oct 2026

Documents

Documents for ATS130N2D73LT

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • UL
  • CE
  • UKCA
  • CCC
  • EAC
  • EN/IEC 60947-4-2
  • UL 60947-4-2
  • IEC 60664-1
Quick answers

Questions about the ATS130

What is the rated current of ATS130?

The rated current of ATS130 is 73 A.

Which supply voltage is ATS130 rated for?

The rated operational voltage of ATS130 is 380–415 V AC.

What motor power is ATS130 rated for?

The rated motor power of ATS130 is 37 kW.

Which control voltage does ATS130 need?

The control voltage range of ATS130 is 24 V.

What is the HS code of ATS130 for customs?

The tariff (HS) code on file for ATS130 is 853710.

What is the EAN of ATS130?

The EAN (GTIN) of ATS130 is 3606486007426.

Where does ATS130 ship from, and how fast?

ATS130 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.

Guides

Guides for soft starters

All guides for soft starters
Reviews

Customer reviews

Series

Schneider Electric ATS130

Brand
Schneider Electric
Series
ATS130
Series page →
Series

Other series in Schneider Altistart Soft Starters

4,559.52 SR Low stock · 16 Nov
Quote

Get a Quote

ATS130

Genuine parts

Genuine, factory-sealed parts

Schneider Electric · ATS130N2D73LT

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Schneider Electric and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart