ABB S200 vs S800: Standard vs High-Performance MCB
ABB S200 and S800 MCBs compared on current rating, breaking capacity, standards, and the point where a feeder outgrows S200 and needs S800.
ABB SH204M-C40 4P type C miniature circuit breaker, In 40 A, 10 kA breaking capacity at 400 V AC, DIN-rail mounted.
Rated 40 A with 10 kA breaking capacity at 400 V AC, the ABB SH204M-C40 (SKU 2CDS274011R0404) is the four-pole, higher-current member of the SH200M miniature circuit breaker series. Its type C tripping characteristic trips instantaneously between 5 and 10 times In, which tolerates the inrush of small motors or transformers on three-phase-plus-neutral circuits, and it mounts on standard DIN rail in a 4-module, 70 mm wide housing.
At In 40 A and 4P, the SH204M-C40 protects three-phase-plus-neutral circuits carrying more current than the lower-current, 2-pole members of the SH200M series, while keeping the same type C instantaneous-trip band (5-10× In) that tolerates motor and transformer inrush. Its 10 kA breaking capacity at 400 V AC covers typical distribution fault levels for this current rating without needing a current-limiting device upstream. Choose the 4-pole format specifically when the neutral conductor must be switched along with the three phases, not just protected.
| Dielectric Test Voltage | 50 / 60 Hz - 1 min 2 kV |
|---|---|
| Power Supply Connection | Arbitrary |
| Contact Position Indication | ON / OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 10000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 4 |
| Number of Poles | 4P |
| Tightening Torque | 2 N·m |
| Screw Terminal Type | Cage Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Connecting Capacity | Conductor 25 / 25 mm², Flexible with Ferrule 0.75 ... 16 mm², Flexible 0.75 ... 16 mm², Rigid 0.75 ... 25 mm², Stranded 0.75 ... 25 mm² |
| Installation Size | acc. to DIN 43880 1 |
| Terminal Type | Screw Terminals |
| Actuator Type | Toggle |
| Tripping Characteristic | C |
|---|---|
| Rated Operational Voltage | acc. to IEC 60898-1 400 V |
| Operational Voltage | Maximum (Incl. Tolerance) 440 V AC, Minimum 12 V AC |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV, at 2000 m 5 kV, at Sea Level 6.2 kV |
| Input Voltage Type | AC |
| Rated Current (In) | 40 A |
| Rated Short-Circuit Capacity | (AC) 10 kA, (400 V AC) 10 kA, (400 V) 10 kA |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | 19.2 W, at Rated Operating Conditions per Pole 4.8 W |
| Overvoltage Category | III |
| Housing Material | Insulation Group II, RAL 7035 |
|---|
| Part number | 2CDS274011R0404 |
|---|---|
| Type designation | SH204M-C40 |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 4016779703055 |
| ETIM class | EC000042 |
| eCl@ss | 27141901 |
| Package Level 1 Units | carton 1 piece |
| Package Level 1 Gross Weight | 0.46 kg |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|---|
| RoHS Date | 20260312 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20260312 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Ambient Air Temperature | Operation -25 ... +55 °C, Storage -40 ... +70 °C |
|---|---|
| Reference Ambient Air Temperature | 30 °C |
| Degree of Protection | IP20, Enclosure with Cover IP40 |
| Pollution Degree | 2 |
| Environmental Conditions | 28 cycles, with 55 °C / 90-96 %, and 25 °C / 95-100 % |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Width in Number of Modular Spacings | 4 |
|---|---|
| Product Net Width | 70 mm |
| Product Net Height | 88 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.44 kg |
| Pole Net Weight | 0.115 kg |
| Built-In Depth (t2) | 69 mm |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
|---|---|
| Mounting Position | any |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
|---|---|
| UNSPSC | 39121603 |
| eClass | V11.0 : 27141901 |
| Standards | IEC/EN 60898-1 |
| Certification Agency | EN, IEC |
| Shipping weight | 0.44 kg |
|---|---|
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of SH204M-C40 is 40 A.
The rated operational voltage of SH204M-C40 is 400 V AC.
The tariff (HS) code on file for SH204M-C40 is 853620.
The EAN (GTIN) of SH204M-C40 is 4016779703055.
SH204M-C40 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
ABB S200 and S800 MCBs compared on current rating, breaking capacity, standards, and the point where a feeder outgrows S200 and needs S800.
A grounded, spec-by-spec comparison of Schneider Acti9 iC60, ABB S200 and Siemens 5SY miniature circuit breakers covering curve availability, breaking-capacity tiers, RCBO options and...
A load-by-load walkthrough matching MCB tripping curves B, C, D, K, and Z to inrush current so the breaker neither nuisance-trips nor under-protects the...