ABB S200 vs S800: Standard vs High-Performance MCB
ABB S200 and S800 MCBs compared on current rating, breaking capacity, standards, and the point where a feeder outgrows S200 and needs S800.
ABB S202M-C8UC miniature circuit breaker, 2P, 8 A, C curve, AC/DC, 10 kA breaking capacity, DIN-rail mount.
At 8 A, the ABB 2CDS272061R0084 S202M-C8UC is a 2-pole miniature circuit breaker in ABB's System pro M compact S200MUC range, with a C tripping characteristic for AC or DC service. It carries a 10 kA breaking capacity (AC) under IEC 60898-1 at up to 400 V AC / 440 V DC and disconnects both poles together.
The 2-pole design disconnects both conductors simultaneously, suited to an L+N circuit or a DC +/- pair rather than two separate single-phase loads. At 8 A, the C curve trips instantaneously at 5-10x In, enough margin for lighting-ballast or small transformer inrush. For higher currents the same S202M-C 2-pole frame extends to 13 A in this range; size the breaker to the actual branch load.
| Dielectric Test Voltage | 50 / 60 Hz - 1 min 2 kV |
|---|---|
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V DC) 25 kA, (230 V AC) 15 kA, (400 V AC) 15 kA, (440 V AC) 10 kA, (440 V DC) 10 kA, (230 V) 10 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V DC) 20 kA |
| Power Supply Connection | Please Note Polarity of Device |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 20000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 2 |
| Number of Poles | 2P |
| Tightening Torque | 2.8 N·m |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Marking | I / O |
| Actuator Material | Insulation Group II, Black, Sealable |
| Options Provided | Universal current |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Remarks | Please note polarity of device |
| Connecting Capacity | Busbar 10/10 mm², Flexible with Ferrule 0.75 ... 25 mm², Flexible 0.75 ... 25 mm², Flexible 0.75 ... 25 mm², Rigid 0.75 ... 35 mm², Stranded 0.75 ... 35 mm² |
| Installation Size | acc. to DIN 43880 1 |
| Terminal Type | Screw Terminals |
| Actuator Type | Toggle |
| Tripping Characteristic | C |
|---|---|
| Rated Operational Voltage | acc. to IEC 60898-1 400 V AC, acc. to IEC 60898-1 440 V DC, acc. to IEC 60898-2 400 V AC, acc. to IEC 60898-2 440 V DC, acc. to IEC 60947-2 440 V AC, acc. to IEC 60947-2 440 V DC |
| Operational Voltage | Maximum (Incl. Tolerance) 440 V AC, Maximum (Incl. Tolerance) 500 V DC, Minimum 12 V AC, Minimum 12 V DC |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV, at 2000 m 5 kV, at Sea Level 6.2 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 8 A |
| Rated Short-Circuit Capacity | (AC) 10 kA, (230 V AC) 10 kA, (253 V AC) 10 kA, (400 V AC) 10 kA, (440 V DC) 10 kA, (230 V) 10 kA, (400 V) 10 kA |
| Rated Frequency (f) | 50 / 60 Hz, DC |
| Power Loss | 3.08 W, at Rated Operating Conditions per Pole 1.54 W |
| Overvoltage Category | III |
| Housing Material | Insulation Group I, RAL 7035 |
|---|
| Part number | 2CDS272061R0084 |
|---|---|
| Type designation | S202M-C8UC |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 4013614432989 |
| ETIM class | EC000042 |
| eCl@ss | 27141901 |
| Package Level 1 Units | carton 5 piece |
| Package Level 1 Gross Weight | 1.21 kg |
| Maximum Operating Voltage UL/CSA | 480Y/277 V AC, 500 V DC |
|---|---|
| Interrupting Rating acc. to UL1077 | (220 V AC) 10 kA, (277 V AC) 6 kA, (440 V DC) 10 kA, (480Y / 277 V AC) 10 kA, (500 V DC) 10 kA |
| Connecting Capacity UL/CSA | Busbar 14-8 AWG, Conductor 14-4 AWG |
| Tightening Torque UL/CSA | 25 in·lb |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|---|
| RoHS Date | 20260312 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20260312 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Ambient Air Temperature | Operation -25 ... +55 °C, Storage -40 ... +70 °C |
|---|---|
| Reference Ambient Air Temperature | 30 °C |
| Degree of Protection | IP20, Enclosure with Cover IP40 |
| Pollution Degree | 3 |
| Environmental Conditions | 28 cycles, with 55 °C / 90-96 %, and 25 °C / 95-100 % |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
| Width in Number of Modular Spacings | 2 |
|---|---|
| Product Net Width | 35 mm |
| Product Net Height | 88 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.234 kg |
| Pole Net Weight | 0.125 kg |
| Built-In Depth (t2) | 69 mm |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
|---|---|
| Mounting Position | any |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
|---|---|
| UNSPSC | 39121603 |
| eClass | V11.0 : 27141901 |
| Standards | IEC/EN 60898-2, IEC/EN 60947-2 |
| Certification Agency | EN, IEC |
| Standardization Body | EN, IEC |
| Shipping weight | 0.234 kg |
|---|---|
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of S202M-C8UC is 8 A.
The rated operational voltage of S202M-C8UC is 400 V AC.
The tariff (HS) code on file for S202M-C8UC is 853620.
The EAN (GTIN) of S202M-C8UC is 4013614432989.
S202M-C8UC ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
ABB S200 and S800 MCBs compared on current rating, breaking capacity, standards, and the point where a feeder outgrows S200 and needs S800.
A grounded, spec-by-spec comparison of Schneider Acti9 iC60, ABB S200 and Siemens 5SY miniature circuit breakers covering curve availability, breaking-capacity tiers, RCBO options and...
A load-by-load walkthrough matching MCB tripping curves B, C, D, K, and Z to inrush current so the breaker neither nuisance-trips nor under-protects the...