ABB S200 vs S800: Standard vs High-Performance MCB
ABB S200 and S800 MCBs compared on current rating, breaking capacity, standards, and the point where a feeder outgrows S200 and needs S800.
ABB S804PV-SP8 4-pole PV DC circuit breaker, In 8 A, Icu/Ics 5 kA at 1500 V DC, energy limiting class 3, DIN-rail mounted.
The ABB S804PV-SP8 (SKU 2CCF019648R0001) is a 4-pole DC circuit breaker built for photovoltaic strings, rated 8 A with a 5 kA breaking capacity at 1500 V DC. It uses an SP release and current-limiting design (energy limiting class 3) to interrupt DC arc faults on the PV side of an inverter, and it mounts on standard DIN rail alongside the rest of the S800 series.
SP denotes a thermal-magnetic release tuned for photovoltaic DC fault current; at In 8 A, this breaker is sized for a single PV string output rather than a combiner box. The 5 kA Icu/Ics rating holds across the full 1500 V DC range, so no derating is needed as the string approaches the breaker's maximum insulation voltage. Energy limiting class 3 keeps let-through energy low, which matters more at low fault currents like this 8 A rating than on the higher-current siblings in the same frame.
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (1500 V DC) 5 kA |
|---|---|
| Rated Service Short-Circuit Breaking Capacity (Ics) | (1500 V DC) 5 kA |
| Energy Limiting Class | 3 |
| Number of Protected Poles | 4 |
| Number of Poles | 4P |
| Release Type | SP |
| Actuator Marking | I / O |
| Accessories Available | Yes |
| Connecting Capacity | Flexible 0 … 50 mm², Rigid 0 … 70 mm² |
| Tripping Characteristic | SP |
|---|---|
| Rated Operational Voltage | acc. to IEC 60947-2 1500 V DC |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1500 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Input Voltage Type | DC |
| Rated Current (In) | 8 A |
| Frequency (f) | 0...0 Hz |
| Rated Frequency (f) | 0 Hz |
| Power Loss | Total 6.96 W, at Rated Operating Conditions per Pole 1.74 W |
| Overvoltage Category | III |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|---|
| RoHS Date | 20211214 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20250313 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Part number | 2CCF019648R0001 |
|---|---|
| Type designation | S804PV-SP8 |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 7612271472214 |
| ETIM class | EC000042 |
| eCl@ss | 27141901 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 1010 g |
| Ambient Air Temperature | Operation -40 ... 70 °C, Storage -40 ... 70 °C |
|---|---|
| Degree of Protection | IP20 |
| Pollution Degree | 2 |
| Width in Number of Modular Spacings | 6 |
|---|---|
| Product Net Width | 105 mm |
| Product Net Height | 99 mm |
| Product Net Depth / Length | 111 mm |
| Product Net Weight | 980 g |
| Built-In Depth (t2) | 82.5 mm |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
|---|---|
| UNSPSC | 39121603 |
| eClass | V11.0 : 27141901 |
| Standards | IEC/EN 60947-2 |
| Shipping weight | 0.98 kg |
|---|---|
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of S804PV-SP8 is 8 A.
The tariff (HS) code on file for S804PV-SP8 is 853620.
The EAN (GTIN) of S804PV-SP8 is 7612271472214.
S804PV-SP8 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
ABB S200 and S800 MCBs compared on current rating, breaking capacity, standards, and the point where a feeder outgrows S200 and needs S800.
A grounded, spec-by-spec comparison of Schneider Acti9 iC60, ABB S200 and Siemens 5SY miniature circuit breakers covering curve availability, breaking-capacity tiers, RCBO options and...
A load-by-load walkthrough matching MCB tripping curves B, C, D, K, and Z to inrush current so the breaker neither nuisance-trips nor under-protects the...