- Home
- All Products
- Siemens 6SL3210-1PB21-0UL0 SINAMICS G120 PM240-2 1.5kW/2.2kW 200-240V VFD Power Module Siemens 6SL3210-1PB21-0UL0 SINAMICS G120 PM240-2 1.5kW/2.2kW 200-240V VFD Power Module
Siemens 6SL3210-1PB21-0UL0 SINAMICS G120 PM240-2 1.5kW/2.2kW 200-240V VFD Power Module
Get Quote
- Description
The Siemens 6SL3210-1PB21-0UL0 is a SINAMICS G120 PM240-2 power module for 1/3AC 200-240V supply, rated 1.50 kW at high overload and 2.20 kW at low overload in the compact FSB frame. It has a built-in braking chopper, ships without an input filter, control unit, or operator panel, and is approved from CU firmware version V4.6 onward. IP20 protection and a 3.0 kg weight suit direct panel mounting in a 291 x 100 x 165 mm footprint.
Technical Specifications
| Order Number (MLFB) | 6SL3210-1PB21-0UL0 |
| EAN | 4042948666258 |
| Brand | Siemens |
| Series | SINAMICS G120 |
| Frame Size | FSB |
| Dimensions (H x W x D) | 291 x 100 x 165 mm |
| Country of Origin | GB |
| Number of phases | 1 / 3 AC |
| Line voltage | 200 ... 240 V ±10 % |
| Line frequency | 47 ... 63 Hz |
| Rated input current (LO) | 24.00 A / 13.90 A |
| Rated input current (HO) | 20.90 A / 12.10 A |
| Number of phases | 3 AC |
| Rated voltage | 230V IEC / 240V NEC |
| Rated power (LO) | 2.20 kW / 3.00 hp |
| Rated power (HO) | 1.50 kW / 2.00 hp |
| Rated output current (LO) | 10.40 A |
| Rated output current (HO) | 7.40 A |
| Max. output current | 15.60 A |
| Pulse frequency | 4 kHz |
| Output frequency for vector control | 0 ... 200 Hz |
| Output frequency for V/f control | 0 ... 550 Hz |
| Power loss | 0.12 kW |
| Cooling | Internal air cooling |
| Cooling air requirement | 0.009 m³/s (0.325 ft³/s) |
| Installation altitude | 1,000 m (3,280.84 ft) |
| Operation LO | -10 ... 40 °C (14 ... 104 °F) |
| Operation HO | -10 ... 50 °C (14 ... 122 °F) |
| Transport | -25 ... 55 °C (-13 ... 131 °F) |
| Net weight | 3.0 kg |
Selection Notes
The dual rating - 1.50 kW at high overload, 2.20 kW at low overload - lets the same FSB module cover a constant-torque load such as a conveyor at the high-overload figure, or a quadratic-torque load such as a fan or pump at the higher low-overload figure; size by the duty class the machine actually needs, not the nameplate maximum. Because the module ships without a filter, add an external EMC filter where the installation must meet conducted-emission limits beyond the unfiltered baseline. The integrated braking chopper covers occasional regeneration, such as a load lowering under gravity, without a separate braking module; a sustained regenerative duty cycle still needs an external braking resistor.