- Home
- All Products
- Siemens 6ES7193-6BP20-0BB0 SIMATIC ET 200SP BaseUnit Type B0 20mm Remote I/O Accessory Siemens 6ES7193-6BP20-0BB0 SIMATIC ET 200SP BaseUnit Type B0 20mm Remote I/O Accessory
Siemens 6ES7193-6BP20-0BB0 SIMATIC ET 200SP BaseUnit Type B0 20mm Remote I/O Accessory
Get Quote
- Description
The Siemens 6ES7193-6BP20-0BB0 is a SIMATIC ET 200SP BaseUnit type B0 (BU20-P12+A4+0B) that carries the P1/P2 backplane bus and 4 AUX terminals to a single I/O module slot, rated 24 V DC or 230 V AC with up to 10 A on the P1/P2 and AUX bus and 5 A on its 12 push-in process terminals. It measures 20 x 117 x 35 mm and weighs 48 g.
Technical Specifications
| SKU | 6ES7193-6BP20-0BB0 |
| Brand | Siemens |
| Series | SIMATIC ET 200SP |
| Product Type Designation | BU type B0 |
| Supply Voltage, P1/P2 bus (DC) | 24 V |
| Supply Voltage, P1/P2 bus (AC) | 230 V |
| Supply Voltage, AUX bus | 24 V DC / 230 V AC |
| Current Carrying Capacity, P1/P2 bus, max. | 10 A |
| Current Carrying Capacity, AUX bus, max. | 10 A |
| Current Carrying Capacity, process terminals, max. | 5 A |
| Number of Slots | 1 |
| Process Terminals | 12, push-in, per slot |
| AUX Terminals | 4, bridged to the left |
| Conductor Cross-Section | 0.14-2.5 mm² (AWG 26-14) |
| Terminal Type | Push-in |
| Potential Separation | Backplane bus / supply voltage: Yes |
| Isolation Tested With | 3 100 V DC |
| Ambient Temperature, horizontal | -30 to 60 °C |
| Ambient Temperature, vertical | -30 to 50 °C |
| Max. Installation Altitude | 2 000 m |
| Width | 20 mm |
| Height | 117 mm |
| Depth | 35 mm |
| Weight, approx. | 48 g |
| EAN | 4025515082057 |
| Country of Origin | DE |
Selection Notes
Type B0 carries 4 AUX terminals bridged to the left and 12 push-in process terminals per slot, which distinguishes it from BaseUnit types that route AUX to the right or provide a different terminal count, so match the type letter to the I/O module's terminal requirement before ordering. The 10 A P1/P2 and AUX bus rating and 5 A process-terminal rating cap what can be drawn through this specific BaseUnit regardless of the I/O module plugged into it, so size the station's power budget against that 10 A bus limit across all BaseUnits sharing the potential group.
Applications
Forms the mounting and wiring base for a single I/O module position in a SIMATIC ET 200SP distributed I/O station, carrying the P1/P2 backplane bus and AUX potential group to that slot.