The Schneider Electric SSD1A335M7C1 is a Harmony SSD1 DIN rail solid state relay rated 35 A with zero-voltage switching, a 90-280 V AC/DC control input, and a 48-600 V AC load output. It mounts on 35 mm DIN rail, switches loads up to 7.46 kW/10 hp at 480 V AC, and carries a 600 V insulation rating.
Technical Specifications
| Reference | SSD1A335M7C1 |
| Brand | Schneider Electric |
| Range | Harmony Solid State Relays |
| Series | SSD1 |
| Product Type | Modular DIN rail relay (solid state) |
| Configuration | Relay configuration, 1 channel, 1 phase |
| Rated Current | 35 A |
| Output Switching Mode | Zero voltage switching |
| Output Voltage | 48...600 V AC |
| Control Circuit Voltage | 90...280 V AC/DC |
| Pick-up / Drop-out Voltage | 90 V AC/DC turn-on / 5 V AC/DC turn-off |
| Input Current Range | 6...10 mA |
| Load Current | 0.2...35 A |
| Inrush Current | 1350 A at 60 Hz |
| Maximum Voltage Drop | < 1.15 V (on-state) |
| Motor Controller Rating | 1.5 kW/2 hp (120V AC) / 3.73 kW/5 hp (240V AC) / 7.46 kW/10 hp (480V AC) |
| Rated Insulation Voltage (Ui) | 600 V |
| Dielectric Strength | 4 kV AC (input/output circuit) |
| Rated Impulse Withstand Voltage | 6 kV |
| Response Time | 20 ms (turn-on) / 30 ms (turn-off) |
| Mounting Support | 35 mm symmetrical DIN rail |
| IP Degree of Protection | IP20 |
| Ambient Air Temperature (Operation) | -40...80 C |
| Net Weight | 0.3 kg |
Certifications & Standards
- UL
- CSA
- UL 508
- CSA C22.2 No 14-13
- IEC 61373 Class B category 1
- IEC 60947-4-3
- IEC 62314
- IEC 60950-1
Selection Notes
SSD1A335M7C1 is the 90-280 V AC/DC control-input variant of the 35 A SSD1 relay, versus a 4-32 V DC control input on other SSD1 parts - pick this version when the control signal comes from a 120/230 V AC circuit, such as a PLC relay output or a 24-240 V control transformer, avoiding a separate interposing relay to step the control signal down to DC. Turn-on/turn-off response (20 ms/30 ms) is slower than the DC-input part's 0.5-cycle rating, reflecting the added input-side rectification and filtering needed for the wider AC/DC control range. Load-side rating (35 A, 48-600 V AC output, 7.46 kW/10 hp at 480 V AC) matches the DC-input 35 A part.