- Home
- All Products
- Schneider Electric RM35BA10 Harmony RM35BA Pump 5A 1CO 208-480V AC Control Relay Schneider Electric RM35BA10 Harmony RM35BA Pump 5A 1CO 208-480V AC Control Relay
Schneider Electric RM35BA10 Harmony RM35BA Pump 5A 1CO 208-480V AC Control Relay
Schneider Electric RM35BA10 Harmony RM35BA Pump 5A 1CO 208-480V AC Control Relay
Get Quote
- Description
The Schneider Electric RM35BA10 is a Harmony RM35BA pump control relay that monitors overcurrent, undercurrent, phase sequence and phase failure on 3-phase or single-phase pump supplies. It switches a single 5 A C/O contact, measures 1-10 A current and 208-480 V AC voltage, and mounts on 35 mm DIN rail.
Technical Specifications
| Reference | RM35BA10 |
| Brand | Schneider Electric |
| Range | Harmony Control Relays |
| Series | RM35BA |
| Product Type | Pump control relay |
| Monitored Parameters | Overcurrent/undercurrent, phase sequence, phase failure (3-phase and single-phase pump) |
| Contacts | 1 C/O |
| Nominal Output Current | 5 A |
| Measurement Range | 1...10 A / 208...480 V AC |
| Rated Nominal Voltage (Un) | 208...480 V AC 50/60 Hz, non self-powered |
| Supply Voltage Limits | 183...528 V AC |
| Time Delay | Adjustable 1...60 s (startup inhibition, Ti) / 0.1...10 s (fault, Tt) |
| Switching Capacity | 1250 VA |
| Maximum Switching Current | 5 A AC/DC |
| Maximum Switching Voltage | 250 V AC/DC |
| Overload Input Current | 11 A permanent / 50 A non-repetitive < 1 s |
| Response Time | < 300 ms (fault event) |
| Overvoltage Category | III |
| Rated Insulation Voltage (Ui) | 400 V |
| IP Degree of Protection | IP20 (terminals) / IP30 (casing) |
| Mounting Support | 35 mm DIN rail |
| Width | 35 mm |
Certifications & Standards
- CE
- C-tick
- CSA
- GOST
- UL
- GL
- IEC 60255-6
Selection Notes
RM35BA10's 1-10 A measurement range on the pump's current line catches both dry-running (undercurrent) and blocked-rotor/overload (overcurrent) faults with one relay, plus phase sequence and phase-loss on the 3-phase supply - four failure modes without four separate devices. The 11 A permanent overload input current rating means the sensing input tolerates sustained overcurrent faults through the 1-60 s startup inhibition window without damage. Its 208-480 V AC measurement range covers both 230/400 V and 460/480 V motor supplies from one part.