- Home
- All Products
- Schneider Electric LV529492 EasyPact CVS250 Vigi Earth-Leakage Add-On Module 3P 30 Circuit Breaker Accessory Schneider Electric LV529492 EasyPact CVS250 Vigi Earth-Leakage Add-On Module 3P 30 Circuit Breaker Accessory
Schneider Electric LV529492 EasyPact CVS250 Vigi Earth-Leakage Add-On Module 3P 30 Circuit Breaker Accessory
Schneider Electric LV529492 EasyPact CVS250 Vigi Earth-Leakage Add-On Module 3P 30 Circuit Breaker Accessory
Get Quote
- Description
The Schneider Electric LV529492 is a 3-pole Vigi earth-leakage add-on module for EasyPact CVS250 moulded case circuit breakers, operating at 200-440 V AC 50/60 Hz with adjustable sensitivity from 30 mA to 10 A. It mounts directly on the device terminals, is self-powered from the distribution voltage even on just 2 phases, and actuates the trip unit directly on an earth-leakage fault.
Technical Specifications
| Reference | LV529492 |
| Brand | Schneider Electric |
| Range of Product | EasyPact CVS100-250 |
| Product or Component Type | Vigi add-on |
| Device Application | Wiring |
| Range Compatibility | EasyPact CVS250 |
| Poles Description | 3P |
| [In] Rated Current | 250 A |
| Earth-Leakage Protection Class | Class A, Class AC |
| Earth-Leakage Sensitivity | 0.03-3 A (Class A), 10 A (Class AC), adjustable |
| Residual Earth-Leakage Time Delay | Adjustable: 0, 60, 150, 300 ms |
| [Ue] Rated Operational Voltage | 200-440 V AC 50/60 Hz |
| Maximum Breaking Time | 800 ms |
| Overvoltage Category | II |
| Electrical Shock Protection Class | Class II |
Certifications & Standards
- IEC 60947-2
Selection Notes
LV529492 is sized for the 250 A EasyPact CVS250 frame specifically, rather than the shared 100/160 A module used on smaller CVS breakers; the 4-pole version of the same module is a separate SKU. Its 30 mA to 10 A adjustable sensitivity and 0-300 ms delay cover both Class A (standard) and Class AC earth-leakage detection, so the same module can be set for either personnel protection at 30 mA or selective fire/equipment protection at higher thresholds. Being self-powered from the line voltage, it needs no auxiliary control supply.