- Home
- All Products
- Schneider Electric LUCL1XBL TeSys U Standard Control Unit 0.35-1.4 A 24 V DC Motor Starter Module Schneider Electric LUCL1XBL TeSys U Standard Control Unit 0.35-1.4 A 24 V DC Motor Starter Module
Schneider Electric LUCL1XBL TeSys U Standard Control Unit 0.35-1.4 A 24 V DC Motor Starter Module
Schneider Electric LUCL1XBL TeSys U Standard Control Unit 0.35-1.4 A 24 V DC Motor Starter Module
Get Quote
- Description
The Schneider Electric LUCL1XBL is a TeSys U magnetic control unit for the smallest motor band in the range, pairing with LUB12, LUB32 or LUB38 power bases for 3-phase motors up to 0.25 kW at 400 V. Its dial-adjustable short-circuit setting runs from only 0.35 to 1.4 A, tripping at 14.2 x Ir, on a 24 V DC control circuit.
Technical Specifications
| SKU | LUCL1XBL |
| Brand | Schneider Electric |
| Range | TeSys U |
| Device Short Name | LUCL |
| Product Type | Magnetic control unit |
| Power Base Compatibility | LUB12, LUB32, LUB38, LUB120, LUB320, LUB380 |
| Rated Operational Voltage (Ue) | 690 V AC |
| Network Frequency | 40...60 Hz |
| Utilisation Category | AC-41, AC-43, AC-44 |
| Motor Power | 0.25 kW at under 400-415 V AC |
| Rated Current Adjustment Range | 0.35-1.4 A |
| Tripping Threshold | 14.2 x Ir +/- 20 percent |
| Control Circuit Voltage (Uc) | 24 V DC |
| Rated Insulation Voltage (Ui) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Fixing Mode | Plug-in (front face) |
| Dimensions (W x H x D) | 45 x 66 x 60 mm |
| Net Weight | 0.135 kg |
| IP Degree of Protection | IP20 front panel and wired terminals, IP40 outside connection zone |
| Ambient Temperature (Operation) | -25 to 70 degC |
Certifications & Standards
- CE
- EAC
- ATEX
- IEC 60947-6-2
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
Selection Notes
This is the lowest current unit in the LUCL lineup, built for sub-kilowatt motors or small fan/pump loads where the 4.5-18 A unit would never see enough current to protect anything. It is the only LUCL control unit that also fits the compact LUB12 power base, so confirm the base size before ordering. Short-circuit protection only — pair it with a drive or soft starter that already handles thermal overload.