- Schneider Electric LUCA12B TeSys U Standard Control Unit 3-12 A 24 V AC Motor Starter Module Schneider Electric LUCA12B TeSys U Standard Control Unit 3-12 A 24 V AC Motor Starter Module
Schneider Electric LUCA12B TeSys U Standard Control Unit 3-12 A 24 V AC Motor Starter Module
Schneider Electric LUCA12B TeSys U Standard Control Unit 3-12 A 24 V AC Motor Starter Module
Get Quote
- Description
The Schneider Electric LUCA12B is a TeSys U standard control unit providing adjustable thermal-magnetic motor protection from 3 to 12 A. Plugged into a LUB12, LUB32, or LUB38 power base, it forms a complete starter-controller with Class 10 overload tripping, phase-failure sensing, and earth-fault detection for 3-phase motors up to 5.5 kW at 400 V, controlled from a 24 V AC supply.
Technical Specifications
| Reference | LUCA12B |
| GTIN | 3389110363913 |
| Brand | Schneider Electric |
| Range | TeSys U |
| Product or Component Type | Standard control unit |
| Device Application | Motor control, motor protection |
| Rated Motor Current Adjustment Range | 3-12 A |
| Thermal Overload Class | Class 10 |
| Tripping Threshold | 14.2 x Ir +/- 20% |
| Phase Failure Sensitivity | Yes |
| Max Motor Power | 5.5 kW at 400 V, 5.5 kW at 500 V, 9 kW at 690 V |
| Control Circuit Voltage (Uc) | 24 V AC |
| Rated Operational Voltage (Ue) | 690 V AC |
| Utilisation Category | AC-41, AC-43, AC-44 |
| Rated Insulation Voltage (Ui) | 690 V |
| Fixing Mode | Plug-in (front face) |
| Dimensions (W x H x D) | 45 x 66 x 60 mm |
| Net Weight | 0.135 kg |
| IP Degree of Protection | IP20 (terminals), IP40 (outside connection zone) |
| Compatible Power Bases | LUB12, LUB32, LUB38, LUB120, LUB320, LUB380 |
Certifications & Standards
- CE
- UL
- CSA
- CCC
- EAC
- IEC 60947-6-2
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
Selection Notes
The LUCA12B's 3-12 A range covers the next motor band up from the LUCA05B, up to 5.5 kW at 400 V, while keeping the same Class 10 trip curve and plugging into the same LUB12/32/38 bases. Since it still inserts into a non-reversing base, fit the LU2B or LU6MB/LU2MB reverser hardware separately if direction reversal is needed. Step up to the LUCA18B if the motor's full-load current exceeds 12 A.