- Home
- All Products
- Schneider Electric C25H3MA220 ComPacT NSX250H 3P 220 A 70 kA MA Fixed Moulded Case Circuit Breaker Schneider Electric C25H3MA220 ComPacT NSX250H 3P 220 A 70 kA MA Fixed Moulded Case Circuit Breaker
Schneider Electric C25H3MA220 ComPacT NSX250H 3P 220 A 70 kA MA Fixed Moulded Case Circuit Breaker
Schneider Electric C25H3MA220 ComPacT NSX250H 3P 220 A 70 kA MA Fixed Moulded Case Circuit Breaker
Get Quote
- Description
The C25H3MA220 is a 3-pole Schneider Electric ComPacT NSX250H moulded case circuit breaker with a 220 A magnetic-only MA trip unit and 70 kA breaking capacity (Icu) at 380/415 V AC. Rated operational voltage (Ue) is 690 V AC. Built for motor protection, it provides instantaneous short-circuit tripping only, at a net weight of 2.4 kg.
Technical Specifications
| SKU / Reference | C25H3MA220 |
| Brand | Schneider Electric |
| Range | ComPacT NSX |
| Series | NSX250H |
| Device application | Motor protection |
| Poles | 3P (3D protected) |
| [In] Rated current | 220 A at 65 °C |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] Rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] Rated impulse withstand voltage | 8 kV |
| [Icu] Breaking capacity | 100 kA at 220/240 V AC, 70 kA at 380/415 V AC, 65 kA at 440 V AC, 50 kA at 500 V AC, 35 kA at 525 V AC, 10 kA at 660/690 V AC |
| [Ics] Service breaking capacity | 100 kA at 220/240 V AC, 70 kA at 380/415 V AC, 65 kA at 440 V AC, 50 kA at 500 V AC, 35 kA at 525 V AC, 10 kA at 660/690 V AC |
| Trip unit | MA (magnetic only) |
| Protection functions | I (instantaneous short-circuit only) |
| [Isd]/[Ii] Instantaneous pick-up adjustment range | 9...14 x In, adjustable (9 settings) |
| Control type | Toggle |
| Mounting mode | Fixed |
| Connection | Front upside, front downside, 35 mm pitch |
| Dimensions (W x H x D) | 105 x 161 x 86 mm |
| Net weight | 2.4 kg |
| IP / IK degree | IP40 / IK07 |
| Pollution degree | 3, conforming to IEC 60664-1 |
| Ambient temperature (operation / storage) | -25…70 °C / -50…85 °C |
Certifications & Standards
- EN/IEC 60947-2
Selection Notes
Like the other MA-equipped breakers in the NSX range, the C25H3MA220 has no thermal element, so it needs a downstream overload relay or motor controller to complete the protection scheme — used alone it protects only against short-circuit, not sustained overload. The 9...14 x In adjustable instantaneous pickup allows the threshold to be set above the motor's starting inrush. For a self-contained breaker with both thermal and magnetic protection at this current and frame, the TM200/TM250 TM-D variants are the alternative.