Schneider Electric C125N360FM ComPacT NS1250N 3P 1250 A 50 kA MicroLogic 6.0 Moulded Case Circuit Breaker
Schneider Electric C125N360FM ComPacT NS1250N 3P 1250 A 50 kA MicroLogic 6.0 Moulded Case Circuit Breaker
Get Quote
- Description
The Schneider Electric C125N360FM is a 3-pole, 1250 A ComPacT NS1250N moulded case circuit breaker rated for 50 kA breaking capacity (Icu) at 380/415 V AC. Fixed-mounted and manually operated, it carries a MicroLogic 6.0 electronic trip unit delivering long-time overload, short-time delay, instantaneous and ground-fault protection, and is rated up to 690 V AC for standard-breaking-capacity distribution duty in the ComPacT NS630b...1600 new generation line.
Technical Specifications
| Reference | C125N360FM |
| Brand | Schneider Electric |
| Range | ComPacT NS630b...1600 new generation |
| Number of poles | 3P |
| [In] Rated current | 1250 A at 50 °C |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] Rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] Rated impulse withstand voltage | 8 kV |
| Breaking capacity (Icu) | 85 kA at 220/240 V AC, 50 kA at 380/415 V AC, 50 kA at 440 V AC, 40 kA at 500/525 V AC, 30 kA at 660/690 V AC (IEC 60947-2) |
| Service breaking capacity (Ics) | 50 kA at 220/240 V AC, 50 kA at 380/415 V AC, 50 kA at 440 V AC, 40 kA at 500/525 V AC, 30 kA at 660/690 V AC (IEC 60947-2) |
| [Icw] Short-time withstand current | 19.2 kA, 1 s (IEC 60947-2) |
| Utilisation category / suitability for isolation | Category B; suitable for isolation (Yes, EN/IEC 60947-2) |
| Trip unit name | MicroLogic 6.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSIG |
| Protection pick-up & time-delay adjustment ranges | Ir (long-time, 9 settings): 0.4...1 x In; Isd (short-time, 9 settings): 1.5...10 x Ir; Ii (instantaneous): Off | 2...15 x In; Ig (ground-fault, 9 settings): 0.3...1 x In for In <= 400 A | 0.2...1 x In for 400 A < In < 1250 A | 500...1200 A for In >= 1250 A |
| Earth-leakage protection | Without |
| Control / mounting | Manually operated, Fixed (Backplate support) |
| Connection (upside / downside) | Front / Front |
| Dimensions (W × H × D) | 210 × 327 × 147 mm |
| Net weight | 14 kg |
| IP / IK degree of protection | IP40 / IK07 |
| Ambient air temperature (operation) | -25…70 °C |
Certifications & Standards
- IECEE CB Scheme
- EN/IEC 60947-2
Selection Notes
The N-frame classification gives the C125N360FM 50 kA Icu at 380/415 V AC, sized for standard distribution duty on the 1250 A frame; where fault levels run higher, the H-frame version of the same frame size delivers a higher Icu without a change in footprint. Its MicroLogic 6.0 trip unit adds ground-fault protection on top of the short-time delay stage carried by the 5.0 (LSI) units in this frame, giving long-time, short-time, instantaneous and ground-fault discrimination (LSIG) in one device. The base MicroLogic 6.0 unit has no digital display — settings are read off the dial markings, with no RMS or energy readout. At 210 mm wide on 3 poles, it suits 3-phase-only distribution with no neutral protection; the 4-pole version of the same frame is available where the neutral conductor must be switched and protected.