- Description
Rated 1000 A with a 50 kA breaking capacity at 380/415 V AC, the C100N360FM is a 3-pole ComPacT NS1000N moulded case circuit breaker from Schneider Electric. The MicroLogic 6.0 trip unit delivers overload (L), short-time delayed short-circuit (S), instantaneous (I) and ground-fault (G) protection, and the device mounts fixed with front connections rated 690 V AC.
Technical Specifications
| Reference | C100N360FM |
| Brand | Schneider Electric |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Number of poles | 3P |
| [In] rated current | 1000 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| Breaking capacity (Icu) | 85 kA at 220/240 V AC, 50 kA at 380/415 V AC, 50 kA at 440 V AC, 40 kA at 500/525 V AC, 30 kA at 660/690 V AC, conforming to IEC 60947-2 |
| Rated service breaking capacity (Ics) | 50 kA at 220/240 V AC, 50 kA at 380/415 V AC, 50 kA at 440 V AC, 40 kA at 500/525 V AC, 30 kA at 660/690 V AC, conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA for 1 s |
| Utilisation category | Category B |
| Suitability for isolation | Yes, conforming to EN/IEC 60947-2 |
| Trip unit name | MicroLogic 6.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSIG (overload (L), short-time delayed short-circuit (S), instantaneous (I) and ground-fault (G) protection) |
| [Ir] long-time pick-up adjustment range | 0.4...1 x In, adjustable, 9 settings |
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir, adjustable, 9 settings |
| [Ii] instantaneous pick-up adjustment range | Off, or 2...15 x In |
| [Ig] ground-fault pick-up adjustment range | 0.3...1 x In (In ≤ 400 A) / 0.2...1 x In (400 A < In < 1250 A) / 500...1200 A (In ≥ 1250 A) |
| Earth-leakage protection | Without |
| Zone selective interlocking (ZSI) | Without |
| Control type | Manually operated |
| Mounting mode | Fixed, backplate-mounted |
| Connection (upside / downside) | Front / Front |
| Dimensions (W x H x D) | 210 x 327 x 147 mm |
| Net weight | 14 kg |
| IP / IK degree of protection | IP40 / IK07 |
Certifications & Standards
- IECEE CB Scheme
- EN/IEC 60947-2
Selection Notes
The MicroLogic 6.0 trip unit on the C100N360FM is configured for overload (L), short-time delayed short-circuit (S), instantaneous (I) and ground-fault (G) protection. Stacking G (ground-fault) on top of L-S-I gives this trip unit adjustable earth-fault tripping as well as time-graded short-circuit discrimination, useful on solidly grounded systems that would otherwise need a separate earth-fault relay. In the NS1000 case size, this N-frame breaker is the standard breaking capacity option (50 kA Icu at 380/415 V AC); the H-frame (70 kA Icu) and the L-frame (150 kA Icu) versions share the same case and accessories but trade breaking capacity for cost or vice versa. The A- and E-suffix trip units in the same frame add an ammeter or energy meter respectively, for installations that want local metering without extra hardware. As a 3-pole unit it protects the three phases only; the 4-pole version of the same frame adds switched or protected neutral handling.