The Schneider Electric C080H35AFM is a 3-pole ComPacT NS800H moulded case circuit breaker rated 800 A, with a 70 kA breaking capacity (Icu) at 380/415 V AC. It is fitted with a MicroLogic 5.0 A trip unit delivering long-time overload, short-time delay and instantaneous short-circuit protection (LSI), is fixed-mounted and manually operated, and carries a 690 V rated operational voltage for industrial distribution switchboards.
Technical Specifications
| SKU / Reference | C080H35AFM |
| Brand | Schneider Electric |
| Range | ComPacT NS800H |
| Number of poles | 3P |
| Rated current [In] | 800 A |
| Rated operational voltage [Ue] | 690 V |
| Rated insulation voltage [Ui] | 800 V |
| Rated impulse withstand voltage [Uimp] | 8 kV |
| Breaking capacity [Icu] | 85 kA Icu at 220/240 V AC 50/60 Hz, 70 kA Icu at 380/415 V AC 50/60 Hz, 65 kA Icu at 440 V AC 50/60 Hz, 50 kA Icu at 500/525 V AC 50/60 Hz, 42 kA Icu at 660/690 V AC 50/60 Hz |
| Service breaking capacity [Ics] | 50 kA at 220/240 V AC 50/60 Hz, 50 kA at 380/415 V AC 50/60 Hz, 50 kA at 440 V AC 50/60 Hz, 40 kA at 500/525 V AC 50/60 Hz, 30 kA at 660/690 V AC 50/60 Hz |
| Short-time withstand current [Icw] | 19.2 kA 1 s conforming to IEC 60947-2 |
| Suitability for isolation | Yes |
| Trip unit | MicroLogic 5.0 A, Electronic, LSI protection |
| Protection adjustment ranges | Ir 0.4...1 x In; tr 12.5…600 s at 1.5 x Ir | 0.5…24 s at 6 x Ir | 0.7…16.6 s at 7.2 x Ir; Isd 1.5...10 x Ir; Ii Off | 2...15 x In |
| Display / measurement | LCD display - Ammeter |
| Zone selective interlocking (ZSI) | With |
| Earth-leakage protection | Without |
| Control type / Mounting mode | Manually operated, Fixed |
| Connection (upside/downside, pitch) | Front / Front, pitch 70 mm |
| Dimensions W x H x D | 210 mm (W) x 327 mm (H) x 147 mm (D) |
| Net weight | 14 kg |
| IP / IK degree of protection | IP40, IK07 |
| Ambient air temperature (operation) | -25…70 °C |
| Standards | IEC 60947-2 |
Certifications & Standards
- IECEE CB Scheme
- EN/IEC 60947-2
Selection Notes
Its LSI trip unit adds an adjustable short-time delay (Isd/tsd) on top of long-time overload and instantaneous protection, which lets this breaker hold position in a selectivity study against downstream devices instead of tripping instantaneously on every fault. Pick the base 2.0-series LI variant instead when the circuit is a final sub-distribution feeder with no coordination requirement. The H-frame rating gives it 70 kA Icu at 380/415 V AC; within the NS800H line this is the breaking-capacity class to pick when the calculated prospective short-circuit current at the installation point is at or below that figure without derating to a higher class.