The Schneider Electric BMXDDM3202K is a Modicon X80 discrete mixed I/O module with 16 transistor inputs and 16 transistor outputs at 24 V DC, built for Modicon M340 and M580 PAC racks. Each output channel switches 0.125 A (3.2 A per module), and the module carries an IP20 rating with a 430,000-hour MTBF.
Technical Specifications
| Reference | BMXDDM3202K |
| Brand | Schneider Electric |
| Range | Modicon X80 |
| GTIN | 3595863910636 |
| Product Type | Discrete I/O module |
| Discrete Inputs | 16 |
| Discrete Outputs | 16, transistor (solid state) |
| Input/Output Voltage | 24 V DC, positive logic |
| Current per Output Channel | 0.125 A |
| Maximum Current per Module | 3.2 A |
| Paralleling of Outputs | Up to 3 channels |
| Input Impedance | 9600 Ohm |
| DC Response Time (typical / max) | 4 ms / 7 ms |
| Current Consumption | 104 mA at 24 V DC, 166 mA at 3.3 V DC |
| MTBF | 430,000 h |
| Insulation Resistance | >10 MOhm at 500 V DC |
| Dielectric Strength | 1500 V AC 50/60 Hz 1 min (output/ground, output/internal logic) |
| Sensor Compatibility | 2-wire/3-wire proximity sensors per IEC 60947-5-2 |
| IP Degree of Protection | IP20 |
| Net Weight | 0.11 kg |
Certifications & Standards
- RCM
- CSA
- EAC
- CE
- UL
- EN 61131-2
- EN 61000-6-4
- EN 61000-6-2
- EN 61010-2-201
Selection Notes
Pick the BMXDDM3202K over the 8-channel variant when a rack slot needs to double the point count within the same footprint — its 3.2 A module current budget is split across 16 outputs (0.125 A each), so it suits distributed low-current loads like PLC-driven indicator banks rather than a few higher-draw actuators. Paralleling up to 3 outputs extends the available current per point when a single channel's 0.125 A is insufficient. The module's voltage-detection thresholds — below 14 V DC flags a sensor or pre-actuator fault, above 18 V DC confirms OK — let the PAC diagnose a broken input wire or a blown output fuse without extra wiring, and the 0.5 A external fast-blow fuse specified per input group protects the module itself from field-side short circuits.