- Home
- All Products
- Schneider Electric A9MEM1591 PowerTag Energy R600 3P or 3P+N 600 A Busbar Cable Mounted Wireless Energy Sensor Schneider Electric A9MEM1591 PowerTag Energy R600 3P or 3P+N 600 A Busbar Cable Mounted Wireless Energy Sensor
Schneider Electric A9MEM1591 PowerTag Energy R600 3P or 3P+N 600 A Busbar Cable Mounted Wireless Energy Sensor
Schneider Electric A9MEM1591 PowerTag Energy R600 3P or 3P+N 600 A Busbar Cable Mounted Wireless Energy Sensor
Get Quote
- Description
The Schneider Electric A9MEM1591 PowerTag Energy R600 is a 3P or 3P+N wireless energy sensor rated 600 A maximum current (100 A base current), on bare or insulated busbars, or cables, via a flexible sensor loop. Its Rope sensor clips around a closed 100 mm busbar or cable loop instead of a breaker body, reading up to 600 A. It reports active energy, active power, current, voltage and power factor to IEC 61557-12 Class 1 accuracy over a 2.4 GHz IEEE 802.15.4 radio link to a PowerTag-compatible concentrator.
Technical Specifications
| SKU | A9MEM1591 |
| Brand | Schneider Electric |
| Range | PowerLogic |
| Product name | PowerTag R600 |
| Form factor | Rope |
| Poles | 3P or 3P+N |
| Maximum current (Imax) | 600 A |
| Basic current (Ib) | 100 A |
| Saturation current | 1200 A |
| Starting current | 400 mA |
| Accuracy class | Class 1 current, active power, active energy, power factor; Class 0.5 voltage (IEC 61557-12) |
| Measured values | Active energy, active power, current, voltage, power factor |
| Mounting location | On bare or insulated busbars, or cables, via a flexible sensor loop |
| Wireless protocol | 2.4-2.4835 GHz radio, IEEE 802.15.4, 10 mW |
| Supply voltage | 100-277 V AC phase-to-neutral / 173-480 V AC phase-to-phase |
| Network frequency | 50 Hz / 60 Hz |
| Max power consumption | 3 VA |
| Overvoltage category | IV |
| Measurement category | IV |
| Compatible gateways | EcoStruxure Panel Server Entry, EcoStruxure Panel Server Universal, EcoStruxure Panel Server Advanced, PowerLogic T300, Harmony Hub, Acti9 PowerTag Link, Acti9 PowerTag Link HD |
| Compatible device ranges | Masterpact MTZ (switch disconnector), Masterpact NW/NT, Compact NS100/NS250/NS400, Acti9 and TeSys devices, rated up to 600 A |
| Colour | White (RAL 9003) |
| IP rating | IP20 |
| IK rating | IK05 |
| Operating temperature | -25 to 70 C |
| Weight | 360 g (from product description; not itemised in the se.com spec table) |
Certifications & Standards
- UL listed
- CE
- DNV Marine
- IEC 61557-12
- IEC 61010-1
- IEC 61010-2-030
- IEC 61326-1
- ETSI EN 300 328
- ETSI EN 301 489-1
Selection Notes
Specify the A9MEM1591 over the 200 A A9MEM1590 once the busbar or cable run carries up to 600 A, such as a Compact NS250/NS400 feeder -- the sensor loop and mounting hardware are identical between the two, only the current-sensing core rating differs. For runs beyond 600 A, step up to the R1000 (A9MEM1592).