- Description
The Siemens 3VM1096-4ED32-0AA0 is a three-pole molded case circuit breaker (MCCB) from the SENTRON 3VM1 series, rated 16 A with a breaking capacity of 36 kA (Icu) at 415 V AC (utilisation class S). It is equipped with the TM210 LI thermal-magnetic trip unit providing overload (L) and instantaneous short-circuit (I) protection. Rated for distribution and motor-feeder protection in low-voltage switchgear up to 500 V AC.
Technical Specifications
| SKU | 3VM1096-4ED32-0AA0 |
| Brand | Siemens |
| Series | 3VM1 |
| Product Type | Molded Case Circuit Breaker (MCCB) |
| Rated Current (In) | 16 A |
| Number of Poles | 3P |
| Trip Unit | TM210 — LI |
| Trip Unit Type | Thermal-Magnetic (TM) |
| Breaking Capacity (Icu) | 36 kA @415V AC (Icu, class S) |
| Icu @240V AC | 55 kA |
| Rated Insulation Voltage (Ui) | 800 V |
| Rated Operating Voltage (Ue) | 500 V AC |
| Power Loss (max) | 11 W |
| Dimensions (H×W×D) | 130 mm × 76.2 mm × 70 mm |
| Weight | 0.961 kg |
Certifications & Standards
- IEC 60947-2
Applications & Use Cases
At 16 A rated current and 36 kA breaking capacity, the 3VM1096-4ED32-0AA0 is dimensioned for feeder, sub-distribution and motor-circuit protection in low-voltage main and sub-distribution boards. The TM210 LI trip unit provides fixed overload and short-circuit protection matched to the rated current.
The IEC Frame enclosure supports fixed mounting in form-separated switchgear (form 2–4) and accepts a range of Siemens 3VA accessories — auxiliary and alarm switches, shunt and undervoltage releases, rotary and motor operators — for adaptation to the specific installation and control scheme.