- Home
- Siemens
- Siemens 6ES7405-0DA02-0AA0 SIMATIC S7-400 PS405 4A DC Power Supply Siemens 6ES7405-0DA02-0AA0 SIMATIC S7-400 PS405 4A DC Power Supply
Siemens 6ES7405-0DA02-0AA0 SIMATIC S7-400 PS405 4A DC Power Supply
Get Quote
- Description
The Siemens 6ES7405-0DA02-0AA0 SIMATIC S7-400 PS405 power supply accepts 24, 48 or 60 V DC input and delivers 5 V DC at 4 A to the backplane bus plus 24 V DC at up to 0.5 A, with a typical active power input of 48 W. It occupies one rack slot, buffers a 20 ms mains failure per the NAMUR recommendation, and weighs 760 g.
Technical Specifications
| SKU | 6ES7405-0DA02-0AA0 |
| Brand | Siemens |
| Series | SIMATIC S7-400 |
| EAN | 4019169141970 |
| Product Type Designation | PS405 |
| Supply Voltage (DC) | 24 / 48 / 60 V DC |
| Input Current | 2 A at 24 V DC, 1 A at 48 V DC, 0.8 A at 60 V DC |
| Inrush Current, max | 18 A, 20 ms full width at half maximum |
| Output, Backplane Bus (5 V DC) | 4 A, no base load required |
| Output, Backplane Bus (24 V DC) | 0.5 A, idling-proof |
| Short-Circuit Protection | Yes |
| Active Power Input, typ | 48 W |
| Power Loss, typ | 16 W |
| Mains Buffering | 20 ms, per NAMUR recommendation |
| Backup Battery (optional) | 2x lithium AA, 3.6 V / 2.2 Ah |
| Slots Required | 1 |
| Overvoltage Category | II |
| Equipment Protection Class | I, with protective conductor |
| Ambient Temperature, Operation | 0 to 60 °C |
| Width | 25 mm |
| Height | 290 mm |
| Depth | 217 mm |
| Weight | 760 g |
Certifications & Standards
- CCC
- BIS
Selection Notes
At 4 A on the 5 V DC backplane bus, the PS405 4 A sizes a single-segment S7-400 rack with light to moderate module loading; check the sum of module backplane-bus current draw against this rating before adding modules. Step up to a higher-current PS405 when the rack's combined 5 V DC load exceeds 4 A or when a second unit is needed for redundant operation.
Applications
Its single-slot footprint and 24/48/60 V DC input fit a battery- or DC-bus-fed S7-400 rack with a modest module count, such as a compact skid controller. The optional lithium backup battery keeps the real-time clock and retentive memory alive through a supply interruption.