- Home
- Power Factor Correction
- Schneider Electric BLRCH571A000B44 VarPlus Can HDuty 57.1 kvar 440 V Power Factor Correction Capacitor Schneider Electric BLRCH571A000B44 VarPlus Can HDuty 57.1 kvar 440 V Power Factor Correction Capacitor
Schneider Electric BLRCH571A000B44 VarPlus Can HDuty 57.1 kvar 440 V Power Factor Correction Capacitor
Schneider Electric BLRCH571A000B44 VarPlus Can HDuty 57.1 kvar 440 V Power Factor Correction Capacitor
Get Quote
- Description
The Schneider Electric BLRCH571A000B44 is a VarPlus Can HDuty power factor correction capacitor rated 57.1 kvar at 440 V, 50 Hz. Its heavy-duty dielectric tolerates network harmonic content up to 20 % and a continuous overcurrent capacity of 1.8 x In, so it keeps correcting power factor on busbars that also feed variable-speed drives, rectifiers and other harmonic-generating loads without overheating.
Technical Specifications
| Reference | BLRCH571A000B44 |
| Brand | Schneider Electric |
| Range | PowerLogic (VarPlus Can HDuty) |
| Product or component type | Heavy duty capacitor |
| Rated reactive power at 440 V, 50 Hz | 57.1 kvar |
| Rated voltage | 440 V AC 50/60 Hz |
| Rated frequency | 50/60 Hz |
| Network harmonic content | <= 20 % |
| Continuous overcurrent capacity | 1.8 x In |
| Maximum permissible voltage | 1.1 x Un (8 hours over 24 hours) |
| Inrush current | 250 x In |
| Losses (dielectric / total) | < 0.2 W/kvar dielectric, < 0.5 W/kVAr total |
| Capacitance tolerance | -5 % to 10 % |
| Maximum switching operations per year | 7000 |
| Service life | 130000 h |
| Connections - terminals | Stud terminals |
| Mounting mode | Upright/horizontal |
| Dimensions (diameter x height) | 136 mm x 321 mm |
| Net weight | 5.3 kg |
| IP degree of protection | IP00 |
| Operating altitude | 2000 m |
| Temperature class | D |
| Ambient air temperature for operation | -25...55 °C |
| Relative humidity | 95 % |
Certifications & Standards
- IEC 60831-1
- IEC 60831-2
Selection Notes
At 57.1 kvar and 440 V, the BLRCH571A000B44 is sized for incomers or filter branches with documented harmonic distortion up to 20% - its 1.8 x In continuous overcurrent capacity and 250 x In inrush rating are built in for duty where variable-speed drives or rectifiers already share the busbar. Pick a smaller HDuty step in the same 440 V family when correcting a lighter non-linear load, or a larger one as the reactive power demand grows. On network segments that stay under 10% harmonic content, the standard-duty EasyLogic range covers the same kvar steps at a lower continuous overcurrent rating.