Schneider Electric GV2LE20 TeSys Deca GV2LE 18 A Manual Starter and Protector
Get Quote
- Description
The Schneider Electric GV2LE20 is a TeSys Deca GV2 manual motor circuit breaker with a fixed magnetic trip unit set for an 18 A line current and a 341 A magnetic tripping point. Rated for 690 V AC, it delivers a 15 kA breaking capacity at 400/415 V (dropping to 3 kA at 690 V) and protects motor branches up to 7.5 kW at 400/415 V without a built-in thermal overload function.
Technical Specifications
| Reference | GV2LE20 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| Product Type | Motor circuit breaker (Manual Starter and Protector) |
| Device Short Name | GV2LE |
| Trip Unit Technology | Magnetic |
| Poles | 3P |
| Line Rated Current [Ith] | 18 A |
| Magnetic Tripping Current | 341 A |
| Rated Operational Voltage [Ue] | 690 V AC 50/60 Hz |
| Rated Insulation Voltage [Ui] | 690 V AC |
| Rated Impulse Withstand Voltage [Uimp] | 6 kV |
| Breaking Capacity [Icu] at 400/415 V | 15 kA |
| Breaking Capacity [Icu] at 690 V | 3 kA |
| Motor Power | 7.5 kW at 400/415 V AC; 9 kW at 500 V AC; 15 kW at 690 V AC |
| Control Type | Toggle switch |
| Suitability for Isolation | Yes (IEC 60947-1) |
| Power Dissipation per Pole | 1.8 W |
| IP Degree of Protection | IP20 |
| IK Degree of Protection | IK04 |
| Mounting | 35 mm DIN rail or panel with adaptor plate |
| Dimensions (W x H x D) | 45 x 89 x 78.5 mm |
| Net Weight | 0.33 kg |
| Ambient Operating Temperature | -20...60 °C |
| GTIN | 3389110517019 |
Certifications & Standards
- CB Scheme
- CE
- UKCA
- CCC
- cULus
- EAC
- BV
- RINA
- EN/IEC 60947-2
- EN/IEC 60947-4-1
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
- IEC/EN 60335-2-40 Annex JJ
Selection Notes
As a magnetic-only trip unit, the GV2LE20 protects against short circuits and locked-rotor surges but has no thermal overload element, so it needs a separate overload relay or a self-protected motor for continuous overload coverage. Its breaking capacity is voltage-dependent: 15 kA at 400/415 V but only 3 kA at 690 V, so on 690 V systems it should sit behind upstream fault-current limiting rather than as the sole interrupting device. At 18 A it covers motors up to 7.5 kW at 400/415 V; heavier loads call for a higher current variant in the same GV2LE range.
Applications
Used as a motor branch disconnector and short-circuit protector ahead of a contactor in TeSys motor starter combinations for pumps, fans and small conveyor drives on 35 mm DIN rail.