{"product_id":"siemens-6ep1961-2ba11-sitop-pse200u-selectivity-module","title":"Siemens 6EP1961-2BA11 SITOP PSE200U 4x0.5-3A 24V Selectivity Module","description":"\u003cp\u003eThe Siemens SITOP PSE200U 6EP1961-2BA11 is a 4-channel selectivity module for 24 V DC systems, taking a 12 A input and splitting it across four outputs each adjustable from 0.5 to 3 A, with a common signaling contact for remote status. It isolates an overloaded branch circuit while the other three channels stay powered.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6EP1961-2BA11\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSiemens\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSITOP PSE200U\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePSE200U, selectivity module 4x3A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput voltage (rated)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput voltage range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e22 ... 30 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput overvoltage capability\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e35 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput current (rated, 24V)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput current per channel, up to 60°C\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAdjustable overload threshold\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.5 ... 3 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eThreshold setting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003evia potentiometer\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eResponse delay, max.\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEfficiency\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e97%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower loss, typ.\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e9 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOvercurrent trip\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIout = 1.0-1.5x setpoint, trip after approx. 5 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCurrent-limit trip\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIout = 1.5x setpoint, trip after typ. 100 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eImmediate shutdown\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIout \u0026gt; setpoint and Vin \u0026lt; 20 V, trip after approx. 0.5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput fuse\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5 A per output (not accessible)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRemote reset\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNon-isolated 24 V input, signal high at \u0026gt; 15 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProtection class IP\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMTBF at 40°C\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e755,915 h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEnclosure (W x H x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e72 x 80 x 72 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSnaps onto DIN rail EN 60715 35x7.5\/15\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eCE\u003c\/li\u003e\n\u003cli\u003eUKCA\u003c\/li\u003e\n\u003cli\u003eEAC\u003c\/li\u003e\n\u003cli\u003eCB\u003c\/li\u003e\n\u003cli\u003eShipbuilding\u003c\/li\u003e\n\u003cli\u003eABS\u003c\/li\u003e\n\u003cli\u003eDNV\u003c\/li\u003e\n\u003cli\u003eEPD\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe 0.5-3 A adjustable threshold per channel and 12 A input current size this module for lower-current 24 V branch circuits than the higher-current 4x10A selectivity modules in the same family; pick this variant when individual branch loads stay under 3 A. The non-isolated 24 V remote reset input lets a PLC clear a tripped channel without manual intervention at the cabinet, and the marine classification approvals (ABS, DNV) make it a fit for shipboard control panels where the plain diagnostics module is not certified.\u003c\/p\u003e\u003ch2\u003eApplications\u003c\/h2\u003e\u003cp\u003eProtects multiple independent 24 V DC branch circuits - sensors, small valve solenoids, remote I\/O nodes - downstream of a single power supply, so a short on one output trips only that channel and the signaling contact reports which one.\u003c\/p\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":53960763703579,"sku":"6EP1961-2BA11","price":157.11,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/siemens-6ep1961-2ba11-sitop-pse200u-selectivity-module.png?v=1789680492","url":"https:\/\/stoklink.com\/products\/siemens-6ep1961-2ba11-sitop-pse200u-selectivity-module","provider":"Stoklink","version":"1.0","type":"link"}