{"product_id":"siemens-6ep1332-4ba00-pm1507-s7-1500-power-supply","title":"Siemens 6EP1332-4BA00 PM 1507 S7-1500 Power Module 24 V DC\/3 A PLC Power Supply","description":"\u003cp\u003eThe Siemens 6EP1332-4BA00 is the PM 1507 power module for the SIMATIC S7-1500 system, delivering a stabilized 24 V DC \/ 3 A output from a single-phase 120\/230 V AC input with automatic range selection. At 87% efficiency and 72 W active power output, it dissipates only 11 W at full load. Galvanic isolation provides SELV \/ ES1 output classification per IEC 62368-1.\u003c\/p\u003e\n\n\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\n\u003ctable\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCatalog No. (MLFB)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6EP1332-4BA00\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEAN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4025515152705\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSiemens\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSIMATIC S7-1500\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Type Designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePM 1507\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eS7-1500 Power Module\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eType of Current Supply\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24 V \/ 3 A\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Network Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1-phase AC\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e120 V (85–132 V) \/ 230 V (170–264 V), automatic range selection\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSupply Voltage at 50 Hz\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e230 V\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSupply Voltage at 60 Hz\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e120 V\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eLine Frequency\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50\/60 Hz (45–65 Hz)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Current at 120 V\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.4 A\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Current at 230 V\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.8 A\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInrush Current (max, 25 °C)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e23 A for 3 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eI²t Value (max)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.3 A²·s\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOvervoltage Overload Capability\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2.3 × Vin rated, 1.3 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMains Buffering Time (min)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e20 ms at Vin = 93\/187 V\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInternal Fuse\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eT 3.15 A \/ 250 V (not accessible)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRecommended Feeder MCB\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 A characteristic B or 6 A characteristic C\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Voltage (rated)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Voltage Tolerance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e± 1 %\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Current (rated)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 A (range: 0–3 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eActive Power Output (typical)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e72 W\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEfficiency\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e87 %\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Loss at Full Load (typical)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e11 W\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eResidual Ripple (max)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 mV\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eVoltage Peak (max)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e150 mV\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSoft Start \/ Output Overshoot\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNo overshoot (soft start)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eVoltage Increase Time (typical)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eResponse Delay (max)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.5 s\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eShort-Circuit Current (typical)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 A for 70 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCurrent Limitation Response Value\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.15–3.6 A (typical 3.4 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eShort-Circuit Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eElectronic shutdown, automatic restart\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOvervoltage Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAdditional control loop, limitation at \u0026lt; 28.8 V\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eParallel Operation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUp to 2 units for increased power\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGalvanic Isolation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eYes — SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProtection Class\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eClass I\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP Rating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eLeakage Current (max \/ typical)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.5 mA \/ 0.4 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl Precision — Input Voltage Fluctuation (slow)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1 %\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl Precision — Input Voltage Fluctuation (rapid ±15%)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1 %\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl Precision — Load Step 50\/100\/50 %\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 %\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl Precision — Load Step 10\/90\/10 %\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 %\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSettling Time (load step, max)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStatus Indication\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eLED green (24 V OK), LED red (error), LED yellow (standby)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Connection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eScrew terminal, 1 × L, N, PE; 0.5–2.5 mm² (removable)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Connection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSpring-loaded terminals, 2 × L+, M; 0.5–2.5 mm² (removable)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0–60 °C (horizontal, natural convection); 0–40 °C (vertical)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStorage \/ Transport Temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-40 to +85 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEnvironmental Category\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIEC 60721 Climate class 3K3, 5–95% RH, no condensation\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEMC — Emitted Interference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEN 55022 Class B\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEMC — Mains Harmonics\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEN 61000-3-2\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEMC — Immunity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEN 61000-6-2\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMTBF at 40 °C\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 611 993 h\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eS7-1500 DIN rail; butt-mountable (0 mm lateral clearance)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRequired Spacing — Top \/ Bottom\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e40 mm \/ 40 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W × H × D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 × 147 × 129 mm (installation height: 205 mm)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.45 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCountry of Origin\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eRO (Romania)\u003c\/td\u003e\n\u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHS Code\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e85044083\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\n\n\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\n\u003cul\u003e\n  \u003cli\u003eCE\u003c\/li\u003e\n  \u003cli\u003eUKCA\u003c\/li\u003e\n  \u003cli\u003eEAC\u003c\/li\u003e\n  \u003cli\u003eRCM\u003c\/li\u003e\n  \u003cli\u003eCB\u003c\/li\u003e\n  \u003cli\u003eUL 508\u003c\/li\u003e\n  \u003cli\u003eCSA C22.2 No. 142\u003c\/li\u003e\n  \u003cli\u003eBIS\u003c\/li\u003e\n  \u003cli\u003eIEC 62368-1\u003c\/li\u003e\n  \u003cli\u003eIEC 61204-7\u003c\/li\u003e\n  \u003cli\u003eEN 55022 Class B\u003c\/li\u003e\n  \u003cli\u003eEN 61000-3-2\u003c\/li\u003e\n  \u003cli\u003eEN 61000-6-2\u003c\/li\u003e\n  \u003cli\u003eABS\u003c\/li\u003e\n  \u003cli\u003eBV\u003c\/li\u003e\n  \u003cli\u003eDNV\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch2\u003eSelection Notes\u003c\/h2\u003e\n\u003cp\u003eThe 6EP1332-4BA00 supplies 3 A at 24 V DC — sufficient for a compact S7-1500 station with a CPU plus a handful of I\/O modules drawing up to 72 W combined. Its 20 ms mains buffering at Vin = 93\/187 V covers brief supply dips without triggering a CPU restart. Where the station load exceeds 3 A, two PM 1507 units can be paralleled without additional hardware. Vertical mounting is permissible but derate the ambient limit to 40 °C; horizontal mounting retains the full 0–60 °C range. Choose the higher-rated PM 1507 5 A variant (6EP1333-4BA00) when module count or powered field devices push the 24 V bus above 72 W.\u003c\/p\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":53960451555611,"sku":"6EP1332-4BA00","price":180.02,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/siemens-6ep1332-4ba00-pm1507-s7-1500-power-supply.png?v=1789641222","url":"https:\/\/stoklink.com\/products\/siemens-6ep1332-4ba00-pm1507-s7-1500-power-supply","provider":"Stoklink","version":"1.0","type":"link"}