{"product_id":"schneider-electric-xpsmcmco0000s1-rs485-safe-module","title":"Schneider Electric XPSMCMCO0000S1 Modicon MCM RS485 Safe Communication Expansion Module Safety PLC","description":"\u003cp\u003eThe Schneider Electric XPSMCMCO0000S1 is a Modicon MCM safe communication expansion module that adds one RS485 port, via a 4-way connector, to an XPSMCM safety controller for safe inter-controller communication. It connects over the backplane expansion connector and cannot operate stand-alone, reaching Category 4 \/ PL e per ISO 13849-1 and SIL 3 per IEC 61508 over a maximum 50 m cable distance.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003eReference\u003c\/td\u003e\n\u003ctd\u003eXPSMCMCO0000S1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange\u003c\/td\u003e\n\u003ctd\u003eModicon MCM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice Short Name\u003c\/td\u003e\n\u003ctd\u003eXPSMCM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSafe communication expansion module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC (-20...+20%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector Type\u003c\/td\u003e\n\u003ctd\u003e4-way RS485\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Ports\u003c\/td\u003e\n\u003ctd\u003e1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Protocol\u003c\/td\u003e\n\u003ctd\u003eRS485 (safe)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e0.125 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMax Cable Distance\u003c\/td\u003e\n\u003ctd\u003e50 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety Level\u003c\/td\u003e\n\u003ctd\u003eCategory 4 \/ PL e (ISO 13849-1), SIL 3 (IEC 61508), SILCL 3 (IEC 62061)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e3 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Support\u003c\/td\u003e\n\u003ctd\u003eOmega 35 mm DIN rail (EN 50022)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP Degree of Protection\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-10...55 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet Weight\u003c\/td\u003e\n\u003ctd\u003e0.3 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (W x H x D)\u003c\/td\u003e\n\u003ctd\u003e22.5 x 99 x 114.5 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eService Life\u003c\/td\u003e\n\u003ctd\u003e20 years\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003ecULus\u003c\/li\u003e\n\u003cli\u003eRCM\u003c\/li\u003e\n\u003cli\u003eTÜV\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eUnlike the CANopen, EtherCAT, EtherNet\/IP and Modbus TCP\/IP modules in the MCM range, the XPSMCMCO0000S1 carries safe RS485 communication rather than non-safe diagnostics - it reaches Category 4 \/ PL e per ISO 13849-1 and SIL 3 per IEC 61508 for linking safety controllers, not just reporting status. It expands an existing Modicon MCM safety controller CPU over the backplane bus and cannot run stand-alone; its 50 m maximum cable distance is shorter than the non-safe fieldbus modules, so route it accordingly within the panel or cell.\u003c\/p\u003e\u003ch2\u003eApplications\u003c\/h2\u003e\u003cp\u003eThe XPSMCMCO0000S1 fits machines that chain two or more XPSMCM safety controllers together - for example a conveyor line split into zones - where each controller's safety decision still needs to reach the next one over a certified safe link rather than a monitoring-only network.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":54074324615451,"sku":"XPSMCMCO0000S1","price":444.19,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-xpsmcmco0000s1-modicon-mcm-rs485-module.jpg?v=1790839081","url":"https:\/\/stoklink.com\/products\/schneider-electric-xpsmcmco0000s1-rs485-safe-module","provider":"Stoklink","version":"1.0","type":"link"}