{"product_id":"schneider-electric-tprst080-tesys-island-motor-starter","title":"Schneider Electric TPRST080 TeSys Island TPRST 66A AC-3 37kW DOL Motor Starter Module","description":"\u003cp\u003eThe Schneider Electric TPRST080 is a TeSys island motor starter rated 66 A at AC-3 for direct-on-line control of motors up to 37 kW at 400 V (80 A at AC-1, up to 690 V). Connected through a TPRBC bus coupler, it provides thermal overload, phase-loss, phase-unbalance, and ground-current protection with a 4-80 A adjustable thermal setting.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTPRST080\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGTIN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3606489832780\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTeSys Island\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMotor starter\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMotor starter type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDirect on line\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePoles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3P, 3 NO\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eUtilisation category\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAC-1, AC-2, AC-3, AC-4, AC-3e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated operational current [Ie]\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e66 A at AC-3 \/ 80 A at AC-1 (\u0026lt;=440 V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMotor power (AC-3)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e37 kW at 380-415\/440\/500\/690 V; 18.5 kW at 230 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated operational voltage [Ue]\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUp to 690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated insulation voltage [Ui]\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V IEC \/ 600 V UL-CSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eThermal protection adjustment range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4-80 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated breaking capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1000 A at 440 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated short-time withstand current [Icw]\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e900 A \/ 1 s, 520 A \/ 10 s at 40 C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl circuit voltage [Uc]\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24 V DC, supplied by the bus coupler\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting mode\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e35 mm symmetrical DIN rail\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.248 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x D x H)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e55 x 125 x 167 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP degree of protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eUL\u003c\/li\u003e\n\u003cli\u003eCSA\u003c\/li\u003e\n\u003cli\u003eCCC\u003c\/li\u003e\n\u003cli\u003eEAC\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-1\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-4-1\u003c\/li\u003e\n\u003cli\u003eUL 60947-4-1\u003c\/li\u003e\n\u003cli\u003eCSA C22.2 No 60947-4-1\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eAt 66 A AC-3 \/ 37 kW, the TPRST080 is the top-current TeSys island starter in this frame, with the widest thermal adjustment range in the lineup at 4-80 A, so it also covers motors well below its full rating without moving to a smaller unit. The 1000 A rated breaking capacity and 900 A \/ 1 s short-time withstand current give it headroom against fault currents when coordinated with an upstream breaker. It has no onboard SIL safety function; where the motor branch needs a certified safe-stop function, a SIL-rated island starter with a safety interface module is the appropriate choice instead.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":50230469591323,"sku":"TPRST080","price":439.21,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-tprst080-tprst-motor-starter.jpg?v=1790283565","url":"https:\/\/stoklink.com\/products\/schneider-electric-tprst080-tesys-island-motor-starter","provider":"Stoklink","version":"1.0","type":"link"}