{"product_id":"schneider-electric-lv480852-isfl160-fuse-switch-disconnector","title":"Schneider Electric LV480852 Fupact ISFL160 3P 160 A NH000\/NH00 Fuse Switch Disconnector","description":"\u003cp\u003eThe Schneider Electric LV480852 is a three-pole Fupact ISFL160 fuse-switch disconnector rated 160 A at 690 V AC for AC-21B duty, sized for NH000\/NH00 fuse links and built for 100 mm busbar, direct mount mounting with m8 terminals. It carries a 100 kA at 415–690 V AC breaking capacity with fuses and a 5 kA for 1 s short-time withstand rating.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eLV480852\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFuPacT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDevice short name\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eISFL160\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePoles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3P, switchable as one 3-pole unit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFuse type \/ size\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDIN NH000\/NH00\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ith] conventional thermal current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e160 A at 40 °C (12 W per fuse)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ue] rated operational voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V AC 50\/60 Hz (800 V AC AC-20); 800 V DC DC-20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ui] \/ [Uimp] insulation \/ impulse withstand voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1000 V AC \/ 1000 V DC \/ 8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ie] rated operational current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e160 A, AC-21B\/AC-22B, 220–690 V AC (80 A at 800 V AC); 160 A, AC-23B, 220–415 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBreaking capacity with fuses\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 kA at 415–690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Icw] rated short-time withstand current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5 kA for 1 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated making\/breaking capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e7.65 kA at 690 V (rated making\/breaking)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFuse carriers handle\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBusbars, 100 mm, direct connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnections \/ tightening torque\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eM8 terminals (14 N.m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D) \/ net weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 mm x 405 mm x 123 mm \/ 1.3 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP degree of protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20 (IEC 60529)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStandard\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIEC 60947-1, IEC 60947-3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eEN\/IEC 60947-1\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-3\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe LV480852 switches all three poles together from a single handle, rated 160 A with a 100 kA at 415–690 V AC breaking capacity with fuses installed. Choose the 100 mm busbar, direct mount variant over the other ISFL160 mounting options when the busbar spacing and cable size in the panel match this connection type.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":50229771043099,"sku":"LV480852","price":131.2,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-lv480852-isfl160-fuse-switch-disconnector.jpg?v=1790869280","url":"https:\/\/stoklink.com\/products\/schneider-electric-lv480852-isfl160-fuse-switch-disconnector","provider":"Stoklink","version":"1.0","type":"link"}