{"product_id":"schneider-electric-lv480806-isft400-fuse-switch-disconnector","title":"Schneider Electric LV480806 Fupact ISFT400 3P 400 A NH2 Fuse Switch Disconnector","description":"\u003cp\u003eThe Schneider Electric LV480806 is a three-pole Fupact ISFT400 fuse-switch disconnector rated 400 A at 690 V AC for AC-21B duty, sized for NH2 fuse links and built for backplate mounting with m10 terminals. It carries a 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC breaking capacity with fuses and a 15.2 kA for 1 s short-time withstand rating.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eLV480806\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFuPacT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDevice short name\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eISFT400\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePoles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3P (3 fuse carriers)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFuse type \/ size\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDIN NH2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ith] conventional thermal current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e400 A at 40 °C (34 W per fuse)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ue] rated operational voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V AC 50\/60 Hz (800 V AC AC-20); 440 V DC (800 V DC DC-20)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ui] \/ [Uimp] insulation \/ impulse withstand voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1000 V AC \/ 1000 V DC \/ 8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ie] rated operational current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e400 A, AC-21B, 220–690 V AC; 400 A, AC-22B, up to 690 V AC; 400 A DC-21B\/DC-22B at 220–440 V DC (3 poles in series)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBreaking capacity with fuses\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Icw] rated short-time withstand current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15.2 kA for 1 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated making\/breaking capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30.4 kA at 690 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFuse carriers handle\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBackplate\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnections \/ tightening torque\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eM10 terminals (20 N.m)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D) \/ net weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e210 mm x 306 mm x 130 mm \/ 2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP degree of protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP3x front face (IEC 60529)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStandard\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIEC 60947-1, IEC 60947-3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eCE\u003c\/li\u003e\n\u003cli\u003eCCC\u003c\/li\u003e\n\u003cli\u003eEAC\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-1\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-3\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe LV480806 is a fixed, non-switchable ISFT400 disconnector rated 400 A, sized for NH2 fuse links and a 80 kA at 415 V AC, 80 kA at 500 V AC, 25 kA at 690 V AC breaking capacity with fuses installed. Pick the backplate version over the other ISFT400 mounting variants in this range when it matches the busbar or cable connection already used in the panel.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":50229769339163,"sku":"LV480806","price":244.83,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-lv480806-isft400-fuse-switch-disconnector.jpg?v=1790869235","url":"https:\/\/stoklink.com\/products\/schneider-electric-lv480806-isft400-fuse-switch-disconnector","provider":"Stoklink","version":"1.0","type":"link"}