{"product_id":"schneider-electric-gv4l03n-tesys-gv4-mpcb","title":"Schneider Electric GV4L03N TeSys GV4 3P 3.5 A 50 kA Magnetic Motor Protection Circuit Breaker (MPCB)","description":"\u003cp\u003eThe Schneider Electric GV4L03N is a TeSys GV4 motor circuit breaker rated 3.5 A at 690 V AC, giving magnetic-only protection for 3-phase motors up to 0.55-0.75 kW at 400 V; it is paired with a separate class 10 or 20 thermal overload relay to complete motor protection. Its magnetic trip is adjustable from 21-49 A, breaking capacity reaches 50 kA at 400 V, and it is operated by a rotary handle via EverLink BTR screw terminals.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGV4L03N\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTeSys GV4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDevice Short Name\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGV4L\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eComponent Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMotor circuit breaker\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDevice Application\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMotor protection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTrip Unit Technology\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMagnetic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePoles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eUtilisation Category\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eCategory A (IEC 60947-2), AC-3 (IEC 60947-4-1)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eLine Rated Current (In)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMagnetic Trip Adjustment Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e21-49 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBreaking Capacity (Icu) at 400\/415 V\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 kA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMotor Power at 400 V\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.55-0.75 kW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eRotary handle\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Operational Voltage (Ue)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V AC, 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Insulation Voltage (Ui)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e800 V AC, 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnections\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEverLink BTR screw terminals, 1.5-70 mm² (top), 2.5-95 mm² (bottom)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP Degree\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP40\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIK Degree\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIK07\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.65 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eIEC\u003c\/li\u003e\n\u003cli\u003eCCC\u003c\/li\u003e\n\u003cli\u003eEAC\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-2\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-4-1\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003ePick the 3.5 A frame for motors up to 0.55-0.75 kW at 400 V; because this breaker only trips magnetically, size the accompanying thermal overload relay (class 10 or 20) to the motor's actual full-load current rather than relying on the breaker alone. The 50 kA breaking capacity at 400 V is common across the whole GV4L\/GV4LE range, so frame selection is driven purely by current rating.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":50230502064411,"sku":"GV4L03N","price":430.96,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-gv4l03n-tesys-gv4-mpcb.jpg?v=1790901379","url":"https:\/\/stoklink.com\/products\/schneider-electric-gv4l03n-tesys-gv4-mpcb","provider":"Stoklink","version":"1.0","type":"link"}