{"product_id":"schneider-electric-g20-25uvr415ac-undervoltage-release","title":"Schneider Electric G20-25UVR415AC GoPact MCCB 200-250 UV Release 380-415 V AC Circuit Breaker Accessory","description":"\u003cp\u003eThe Schneider Electric G20-25UVR415AC is an MN undervoltage release built for a 415 V AC 50\/60 Hz control circuit, fitting both the GoPact MCCB 200 and GoPact MCCB 250. Opening is guaranteed once the supply voltage falls below 0.35 times Un, possible but not guaranteed up to 0.7 times Un, and the breaker is held closed once the supply recovers above 0.85 times Un. Maximum response time is 25 ms.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eG20-25UVR415AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGoPact MCCB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct \/ Component Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eVoltage release\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDevice Short Name\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDevice Application\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eControl\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCompatible Breakers\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGoPact MCCB 200, GoPact MCCB 250\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelease Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUndervoltage release\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Uc] Control Circuit Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e415 V AC 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eThreshold Tripping Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.35...0.7 Un opening, 0.85...1.1 Un closing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax Holding Power Consumption\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.5 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMax Pick-up Power Consumption\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eResponse Time\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e25 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eUse the 415 V AC coil version instead of the 240 V AC G20-25UVR240AC when the panel control circuit already runs at 380\/415 V AC, which removes the need for a separate step-down transformer feeding this release. Because the opening threshold tracks a percentage of Un rather than an absolute voltage, the trip point scales with the supply it is wired to, so confirm the actual control-circuit voltage before ordering.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":54076349776155,"sku":"G20-25UVR415AC","price":47.17,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-g20-25uvr415ac-gopact-mccb-200-250-undervoltage-release.jpg?v=1790868971","url":"https:\/\/stoklink.com\/products\/schneider-electric-g20-25uvr415ac-undervoltage-release","provider":"Stoklink","version":"1.0","type":"link"}