{"product_id":"schneider-electric-e125f320fm","title":"Schneider Electric E125F320FM EasyPact CVS1250F 3P 1250 A 36 kA ETS 2.0 Fixed Moulded Case Circuit Breaker","description":"\u003cp\u003eThe Schneider Electric E125F320FM is a 1250 A EasyPact CVS1250F moulded case circuit breaker for low-voltage electrical distribution, built on a standard-breaking F frame. Its ETS 2.0 electronic trip unit gives adjustable long-time overload and instantaneous short-circuit protection (LI), and the 3-pole, 3D frame breaks 36 kA at 380\/415 V AC under IEC 60947-2.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003eSKU \/ Reference\u003c\/td\u003e\n\u003ctd\u003eE125F320FM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange\u003c\/td\u003e\n\u003ctd\u003eEasyPact CVS1250F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice application\u003c\/td\u003e\n\u003ctd\u003eLow-voltage electrical distribution\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePoles\u003c\/td\u003e\n\u003ctd\u003e3P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtected poles\u003c\/td\u003e\n\u003ctd\u003e3D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated current [In]\u003c\/td\u003e\n\u003ctd\u003e1250 A at 50 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated operational voltage [Ue]\u003c\/td\u003e\n\u003ctd\u003e440 V AC 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated insulation voltage [Ui]\u003c\/td\u003e\n\u003ctd\u003e800 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated impulse withstand voltage [Uimp]\u003c\/td\u003e\n\u003ctd\u003e8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBreaking capacity [Icu]\u003c\/td\u003e\n\u003ctd\u003e50 kA at 220\/240 V AC, 36 kA at 380\/415 V AC, 36 kA at 440 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eService breaking capacity [Ics]\u003c\/td\u003e\n\u003ctd\u003e50 kA at 220\/240 V AC, 36 kA at 380\/415 V AC, 36 kA at 440 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTrip unit\u003c\/td\u003e\n\u003ctd\u003eETS 2.0, electronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTrip unit rating\u003c\/td\u003e\n\u003ctd\u003e1250 A at 50 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection functions\u003c\/td\u003e\n\u003ctd\u003eLI (long-time overload + instantaneous short-circuit)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLong-time pickup adjustment [Ir]\u003c\/td\u003e\n\u003ctd\u003e0.4...1 x In, adjustable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInstantaneous pickup adjustment [Ii]\u003c\/td\u003e\n\u003ctd\u003e1.5...10 x Ir, adjustable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eControl type\u003c\/td\u003e\n\u003ctd\u003eToggle, rotary handle\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eFixed, backplate support\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection\u003c\/td\u003e\n\u003ctd\u003eFront (upside and downside), 70 mm pitch\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (W x H x D)\u003c\/td\u003e\n\u003ctd\u003e210 x 327 x 147 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet weight\u003c\/td\u003e\n\u003ctd\u003e14 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDegree of protection\u003c\/td\u003e\n\u003ctd\u003eIP40, IK07\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient temperature\u003c\/td\u003e\n\u003ctd\u003e-25...70 °C operation, -50...85 °C storage\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eEN\/IEC 60947-2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eCCC\u003c\/li\u003e\n\u003cli\u003eCB\u003c\/li\u003e\n\u003cli\u003eCE\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-2\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003ePick the F frame where available fault current stays under 36 kA at 380\/415 V; it is the lightest-duty, lowest-cost frame in this CVS range. The 3-pole frame protects the three phase conductors only; use it on a balanced three-phase feeder where the neutral is bonded upstream or not distributed. Within the 1250 A CVS1250 frame size, E125F320FM (F class) sits alongside breaking-class siblings at the same amperage -- move up a class if downstream fault studies show higher prospective short-circuit current than 36 kA at 380\/415 V, since the ETS 2.0 long-time setting only trims down to 0.4 x In (500 A) and cannot raise the frame's current rating.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":54076254617883,"sku":"E125F320FM","price":1511.37,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-e125f320fm-cvs1250f-moulded-case-circuit-breaker.jpg?v=1790868376","url":"https:\/\/stoklink.com\/products\/schneider-electric-e125f320fm","provider":"Stoklink","version":"1.0","type":"link"}