{"product_id":"schneider-electric-c160n42efm-compact-ns1600n-mccb","title":"Schneider Electric C160N42EFM ComPacT NS1600N 4P 1600 A 50 kA MicroLogic 2.0 E Moulded Case Circuit Breaker","description":"\u003cp\u003eThe Schneider Electric C160N42EFM is a 4-pole, 1600 A ComPacT NS1600N moulded case circuit breaker rated for a breaking capacity of 50 kA at 380\/415 V AC. It carries a MicroLogic 2.0 E electronic trip unit with long-time and instantaneous (LI) protection and an operational voltage of 690 V AC, suited for fixed, manually-operated distribution boards up to 1600 A.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSKU \/ Reference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eC160N42EFM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange of Product\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eComPacT NS630b...1600 new generation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eCircuit breaker\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of poles\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4P (4D protected, neutral position left)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[In] Rated current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1600 A at 50 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ue] Rated operational voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e690 V AC 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ui] \/ [Uimp] Insulation \/ impulse withstand voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e800 V AC \/ 8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Icu] Breaking capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e85 kA at 220\/240 V AC, 50 kA at 380\/415 V AC, 50 kA at 440 V AC, 40 kA at 500\/525 V AC, 30 kA at 660\/690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ics] Rated service breaking capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e37 kA at 220\/240 V AC, 37 kA at 380\/415 V AC, 37 kA at 440 V AC, 30 kA at 500\/525 V AC, 22 kA at 660\/690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Icw] Rated short-time withstand current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e19.2 kA, 1 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTrip unit\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMicroLogic 2.0 E\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTrip unit protection functions\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eLI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ir] Long-time pick-up adjustment range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.4...1 x In (adjustable, 9 settings)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e[Ii] Instantaneous pick-up adjustment range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.5...10 x Ir\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNeutral protection setting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNo protection (3D) | 0.5 x Ir (3D + N\/2) | 1 x Ir (4D)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eZone selective interlocking (ZSI)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eWithout\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eType of measurement\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEnergy meter\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting mode \/ Control type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFixed, manually operated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (W x H x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e280 x 327 x 147 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e18 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP degree of protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP40\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eIECEE CB Scheme\u003c\/li\u003e\n\u003cli\u003eEN\/IEC 60947-2\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe MicroLogic 2.0 E trip unit on the C160N42EFM provides long-time overload (L) and instantaneous short-circuit (I) protection only — there is no short-time delay stage, so this 4-pole, 1600 A breaker suits a terminal or feeder position rather than a selective main incomer. The 'E' suffix extends the display to an energy meter, adding kWh measurement on top of the ammeter function. Step up to the 5.0 (LSI) trip unit in the same NS1600N frame when the installation needs short-time discrimination with downstream devices, or to 6.0 (LSIG) when ground-fault tripping must also be integrated.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":54076243640603,"sku":"C160N42EFM","price":3445.04,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-c160n42efm-compact-ns1600n-mccb.jpg?v=1790868158","url":"https:\/\/stoklink.com\/products\/schneider-electric-c160n42efm-compact-ns1600n-mccb","provider":"Stoklink","version":"1.0","type":"link"}