{"product_id":"schneider-electric-c10s2tm016-compact-nsx100s-2p-16a-mccb","title":"Schneider Electric C10S2TM016 ComPacT NSX100S 2P 16 A 70 kA TM-D Fixed Moulded Case Circuit Breaker","description":"\u003cp\u003eSchneider Electric's C10S2TM016 is a 2-pole ComPacT NSX100S moulded case circuit breaker rated 16 A, delivering 70 kA breaking capacity (Icu) at 415 V AC and a 690 V AC operational voltage (Ue). This frame is also DC-rated up to 500 V DC. Its TM-D thermal-magnetic trip unit pairs fixed overload protection with a fixed 190 A instantaneous short-circuit trip, fixed-mounted for low-voltage distribution boards.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003eReference\u003c\/td\u003e\n\u003ctd\u003eC10S2TM016\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange\u003c\/td\u003e\n\u003ctd\u003eComPacT NSX\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDevice short name\u003c\/td\u003e\n\u003ctd\u003eNSX100S\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePoles\u003c\/td\u003e\n\u003ctd\u003e2P\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtected poles\u003c\/td\u003e\n\u003ctd\u003e2D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[In] Rated current\u003c\/td\u003e\n\u003ctd\u003e16 A at 40 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ue] Rated operational voltage\u003c\/td\u003e\n\u003ctd\u003e690 V AC 50\/60 Hz | 500 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork type\u003c\/td\u003e\n\u003ctd\u003eAC | DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ui] Rated insulation voltage\u003c\/td\u003e\n\u003ctd\u003e800 V AC 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uimp] Rated impulse withstand voltage\u003c\/td\u003e\n\u003ctd\u003e8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBreaking capacity (Icu)\u003c\/td\u003e\n\u003ctd\u003e100 kA at 220\/240 V AC, 70 kA at 380\/415 V AC, 65 kA at 440 V AC, 35 kA at 500\/525 V AC, 10 kA at 660\/690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eService breaking capacity (Ics)\u003c\/td\u003e\n\u003ctd\u003e100 kA at 220\/240 V AC, 70 kA at 380\/415 V AC, 65 kA at 440 V AC, 35 kA at 500\/525 V AC, 10 kA at 660\/690 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTrip unit\u003c\/td\u003e\n\u003ctd\u003eTM-D, thermal-magnetic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTrip unit protection functions\u003c\/td\u003e\n\u003ctd\u003eLI (overload + short-circuit)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ir] Long-time pick-up adjustment\u003c\/td\u003e\n\u003ctd\u003e1 x In (fixed)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ii] Instantaneous pick-up\u003c\/td\u003e\n\u003ctd\u003e190 A (fixed)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEarth-leakage protection\u003c\/td\u003e\n\u003ctd\u003eWithout\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eControl type\u003c\/td\u003e\n\u003ctd\u003eToggle\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting mode\u003c\/td\u003e\n\u003ctd\u003eFixed\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection pitch\u003c\/td\u003e\n\u003ctd\u003e35 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions W x H x D\u003c\/td\u003e\n\u003ctd\u003e70 mm x 161 mm x 86 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet weight\u003c\/td\u003e\n\u003ctd\u003e1.2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP \/ IK degree\u003c\/td\u003e\n\u003ctd\u003eIP40 \/ IK07\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient temperature (operation)\u003c\/td\u003e\n\u003ctd\u003e-25…70 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating altitude\u003c\/td\u003e\n\u003ctd\u003e0-2000 m without derating, derated up to 5000 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eEN\/IEC 60947-2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\u003cli\u003eEN\/IEC 60947-2\u003c\/li\u003e\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe S-coded 2-pole frame is rated 70 kA Icu at 380\/415 V AC and is also DC-rated (100 kA at 250 V DC on one pole, 100 kA at 500 V DC with two poles in series), making it suited to mixed AC\/DC low-voltage circuits such as DC bus or battery protection alongside standard AC use. Its TM-D thermal-magnetic trip unit combines the LI protection set in one block: L is the overload (thermal) function, fixed at 1 × In, and I is the short-circuit (magnetic) function, fixed at 190 A. Within the same NSX100S frame, pick the 16 A trip rating to match the protected circuit's full-load current — lower- and higher-current variants share the same breaking capacity and enclosure footprint.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":50229606220059,"sku":"C10S2TM016","price":192.79,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-c10s2tm016-nsx100s-mccb.jpg?v=1790868517","url":"https:\/\/stoklink.com\/products\/schneider-electric-c10s2tm016-compact-nsx100s-2p-16a-mccb","provider":"Stoklink","version":"1.0","type":"link"}