{"product_id":"schneider-electric-c10f2tm040-nsx100f-40a-mccb","title":"Schneider Electric C10F2TM040 ComPacT NSX100F 2P 40 A 18 kA at 415 V TM-D Fixed Moulded Case Circuit Breaker","description":"\u003cp\u003eThe Schneider Electric C10F2TM040 is a 2P ComPacT NSX100F moulded case circuit breaker rated 40 A, dual-rated for AC (690 V) and DC (500 V) circuits, with an 18 kA breaking capacity (Icu) at 415 V AC. It uses a fixed, non-adjustable TM-D thermal-magnetic trip unit, giving compact, low-maintenance overload and short-circuit protection in small-frame distribution and DC applications.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003eSKU\u003c\/td\u003e\n\u003ctd\u003eC10F2TM040\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRange\u003c\/td\u003e\n\u003ctd\u003eComPacT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct name \/ device\u003c\/td\u003e\n\u003ctd\u003eComPacT NSX100F\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePoles \/ protected poles\u003c\/td\u003e\n\u003ctd\u003e2P \/ 2D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[In] Rated current\u003c\/td\u003e\n\u003ctd\u003e40 A at 40 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNetwork type\u003c\/td\u003e\n\u003ctd\u003eAC | DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ue] Rated operational voltage\u003c\/td\u003e\n\u003ctd\u003e690 V AC 50\/60 Hz, 500 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ui] Rated insulation voltage\u003c\/td\u003e\n\u003ctd\u003e750 V AC 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Uimp] Rated impulse withstand voltage\u003c\/td\u003e\n\u003ctd\u003e8 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Icu] Breaking capacity\u003c\/td\u003e\n\u003ctd\u003e36 kA at 220\/240 V AC, 18 kA at 380\/415 V AC, 15 kA at 440 V AC, 10 kA at 500\/525 V AC, 5 kA at 660\/690 V AC, 36 kA at 250 V DC (1 pole), 36 kA at 500 V DC (2 poles in series)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBreaking capacity code\u003c\/td\u003e\n\u003ctd\u003eF 18 kA 415 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUtilisation category\u003c\/td\u003e\n\u003ctd\u003eCategory A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSuitability for isolation\u003c\/td\u003e\n\u003ctd\u003eYes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTrip unit\u003c\/td\u003e\n\u003ctd\u003eTM-D (Thermal-magnetic)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTrip unit protection functions\u003c\/td\u003e\n\u003ctd\u003eLI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ir] Long-time pick-up\u003c\/td\u003e\n\u003ctd\u003e1 x In — Fixed\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e[Ii] Instantaneous pick-up\u003c\/td\u003e\n\u003ctd\u003e500 A — Fixed\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting mode \/ support\u003c\/td\u003e\n\u003ctd\u003eFixed, Backplate\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eControl type\u003c\/td\u003e\n\u003ctd\u003eToggle\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection (upside\/downside)\u003c\/td\u003e\n\u003ctd\u003eFront \/ Front\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions W x H x D\u003c\/td\u003e\n\u003ctd\u003e70 x 161 x 86 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNet weight\u003c\/td\u003e\n\u003ctd\u003e1.2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP \/ IK degree of protection\u003c\/td\u003e\n\u003ctd\u003eIP40 \/ IK07\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAmbient air temperature (operation)\u003c\/td\u003e\n\u003ctd\u003e-25...70 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\u003cli\u003eEN\/IEC 60947-2\u003c\/li\u003e\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe TM-D trip unit on this NSX100F frame is fixed rather than adjustable: L overload protection is set at 1 x In and I instantaneous protection trips at 500 A, so the 40 A rating itself is the only selection variable — pick it to sit just above the circuit's full-load current. The 2-pole version covers both single-phase line-to-line AC circuits and two-wire DC circuits where both conductors must be switched and protected together. Because the breaker is dual-rated for AC and DC, the same part also fits DC distribution and battery circuits up to 500 V DC, where the 18 kA AC Icu figure does not apply and the 36 kA DC rating governs instead.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":50229587542299,"sku":"C10F2TM040","price":153.24,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-c10f2tm040-nsx100f-mccb.jpg?v=1790868251","url":"https:\/\/stoklink.com\/products\/schneider-electric-c10f2tm040-nsx100f-40a-mccb","provider":"Stoklink","version":"1.0","type":"link"}