{"product_id":"schneider-electric-bmxart0414-x80-4ch-rtd-thermocouple-input","title":"Schneider Electric BMXART0414 Modicon X80 4-Channel Isolated RTD\/Thermocouple Input Module PLC I\/O Module","description":"\u003cp\u003eThe Schneider Electric BMXART0414 is a Modicon X80 analog input module with 4 isolated, low-level channels for RTD and thermocouple temperature sensors, at 15-bit + sign resolution. It supports Cu10, Ni100, Ni1000, Pt100, and Pt1000 RTDs plus B, E, J, K, L, N, R, S, T, U thermocouples, with external cold-junction compensation.\u003c\/p\u003e\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBMXART0414\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRange\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGTIN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3595863910186\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog input module, isolated, low level\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Types\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eRTD (Cu10, Ni100, Ni1000, Pt100, Pt1000), thermocouple (B, E, J, K, L, N, R, S, T, U), mV (±40 to ±1280 mV)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAnalog\/Digital Conversion\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSigma-delta 16-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Resolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15-bit + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIsolation Between Channels\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIsolated, 750 V DC between channels, 1400 V DC to bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCold Junction Compensation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eExternal, by Pt100 probe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCommon Mode Rejection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e120 dB (50\/60 Hz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNominal Read Cycle Time\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e200 ms (thermocouple), 400 ms (RTD)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMeasurement Resolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1 °C (RTD\/thermocouple)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCurrent Consumption\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e150 mA at 3.3 V DC, 40 mA at 24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMTBF\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1,400,000 h\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIP Degree of Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAmbient Temperature, Operation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0...60 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAmbient Temperature, Storage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-40...85 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNet Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.135 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\u003ch2\u003eCertifications \u0026amp; Standards\u003c\/h2\u003e\u003cul\u003e\n\u003cli\u003eCE\u003c\/li\u003e\n\u003cli\u003eEAC\u003c\/li\u003e\n\u003cli\u003eRCM\u003c\/li\u003e\n\u003cli\u003eUL\u003c\/li\u003e\n\u003cli\u003eMerchant Navy\u003c\/li\u003e\n\u003cli\u003eCSA\u003c\/li\u003e\n\u003cli\u003eIEC 61131-2\u003c\/li\u003e\n\u003cli\u003eIEC 61000-6-4\u003c\/li\u003e\n\u003cli\u003eIEC 61000-6-2\u003c\/li\u003e\n\u003cli\u003eEN 61010-2-201\u003c\/li\u003e\n\u003c\/ul\u003e\u003ch2\u003eSelection Notes\u003c\/h2\u003e\u003cp\u003eThe BMXART0414 reads RTD or thermocouple sensors wired through a Telefast connection sub-base into one Modicon X80 rack slot — each of its 4 isolated channels accepts Cu10, Ni100, Ni1000, Pt100, or Pt1000 RTDs, or B, E, J, K, L, N, R, S, T, U thermocouples, with external cold-junction compensation via a Pt100 probe. Choose it over a standard process-signal analog input card whenever the field signal is a temperature sensor rather than 4-20mA or ±10V, since its sigma-delta 16-bit conversion and 0.1 °C measurement resolution are tuned for low-level millivolt inputs rather than higher-level process ranges.\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":54072509235483,"sku":"BMXART0414","price":584.97,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0903\/7722\/4475\/files\/schneider-electric-bmxart0414-x80-4-ch-rtd-thermocouple-input.jpg?v=1790804185","url":"https:\/\/stoklink.com\/products\/schneider-electric-bmxart0414-x80-4ch-rtd-thermocouple-input","provider":"Stoklink","version":"1.0","type":"link"}